11.0 APPENDIX TO SOFTWARE STRATEGY
11.2 BACNET OBJECT LIST (BY INSTANCE NUMBER)
LCD Browser
Name
Description
Type
BACnet
Units
Default
Page
Object
Value
Instance
Number
12
Frost Prot. Temp
Supply temperature at which frost protection
AV
10275
Degrees-Celsius
4
becomes active
12
Heat Boost Setpoint
Heater Boost Setpoint
AV
10276
Degrees-Celsius
35
12
High Temp Alarm
Supply temp which will trip the high
AV
10277
Degrees-Celsius
50
supply alarm
12
Humidity Target
Relative Humidity Target
AV
10278
Percent-relative-Humidity
50
13
IO Damper Delay
Delay between starting the fan relay and the
AV
10279
Seconds
0
fan output
13
Low Temp Alarm
Supply temp which will trip the low supply alarm
AV
10280
Degrees-Celsius
8
13
Night C Fan Speed
The night cool fan speed
AV
10281
Percent
60
13
Night C Min Temp
The minimum temperature that will stop
AV
10302
Degrees-Celsius
12
night cooling
14
Pressure Target
Target pressure value
AV
10303
Pascals
400
14
Purge Fan Speed
Purge Fan Speed
AV
10304
Percent
60
14
Purge Min Temp
The minimum temperature that will stop
AV
10305
Degrees-Celsius
12
night cooling
14
RTC Boost Band
The Return Temperature Control Boost Band
AV
10306
Degrees-Celsius
15
15
RTC Max Supply Temp Maximum supply temp when in RTC mode
AV
10307
Degrees-Celsius
35
15
RTC Min Supply Temp
Minimum supply temp when in RTC mode
AV
10308
Degrees-Celsius
12
15
Software Setpoint
Software Setpoint
AV
10309
Degrees-Celsius
22
15
STC H/C Pref
STC Heat/Cool Pref
AV
10310
No units
50
16
STC HX Efficiency
STC HX Efficiency
AV
10311
No units
0.8
16
Supply Fan Max
Individual fan maximum speed setting
AV
10312
Percent
100
16
Supply Fan Min
Individual fan minimum speed setting
AV
10314
Percent
20
16
Trickle Deadband
Setpoint deadband used when trickling with
AV
10316
Degrees-Celsius
5
no enable signal.
17
Room Air Temp
The room air temperature
AV
11296
Degrees-Celsius
N/A
17
CO2 Level
The CO2 Level
AV
13980
ppm
N/A
17
Humidity
The Humidity Level
AV
14297
% RH
N/A
17
Active Setpoint
The setpoint currently used
AV
14534
Degrees-Celsius
N/A
18
EF Max Volt
The upper voltage for the extract fan
AV
17273
Volts
10
18
EF Start Volt
The voltage required to start the extract fan
AV
17274
Volts
1
18
SF Max Volt
The upper voltage for the supply fan
AV
17275
Volts
10
18
SF Start Volt
The voltage required to start the extract fan
AV
17276
Volts
1
19
SL Enable
The state of the enable input (IN8)
BI
10161
Off/On
N/A
19
SL2 Input
The state of the configurable input (IN9)
BI
10164
Off/On
N/A
19
Alarm Circuit 1
The state of Alarm Circuit 1
BI
10167
Normal/Alarm
N/A
19
Alarm Circuit 2
The state of Alarm Circuit 2
BI
10170
Normal/Alarm
N/A
20
Bypass Damper Cmd
The controller’s signal to the bypass damper.
BO
10185
Open/Close (Open = HX,
N/A
(Close=Bypass)
Close = Bypass)
20
Fault Relay Cmd
The state of the fault relay. (Fault = De-energised)
BO
10188
Alarm/Normal
N/A
20
Fan Enabled Cmd
The state of the fan enabled relay
BO
10191
Off/On
N/A
20
Cooling Demand Cmd The state of the cooling demand relay
BO
10194
Off/On
N/A
30. 11. 15. Leaflet Number 671710
Summary of Contents for ecosmart CONNECT XBOXER XBC
Page 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Page 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...