Parameter Name
Description
Default Setting
Device Name
It defines the BACnet Device Object Name
FAD0351
Device ID
It defines the BACnet Device Object Identifier
127
MAC Address
MSTP Address of FAD
127
Descriptions
BACnet Description of FAD
Field Advanced Display
Baud Rate
It defines the FAD communication speed
38400
over the BACnet local network.
Max Info Frames
It defines the BACnet Device Object Max_Info_Frames
3
Adjust Priority
The Adjust priority parameter defines with which
16
priority the display will command AV / BV / MV values.
Override Priority
The Override priority parameter defines with which
8
priority the display will command AO / BO / MO values
Page Refresh Time
It defines the polling speed at which the FAD will refresh
30 sec
the values shown on the screen
Max Master
This parameter represents the value of the Max_Master
127
property of the node's Device object
APDU Time
The APDU Timeout property defines the amount of time,
3
in seconds, the FAD waits for responses from other devices.
9.6.2 DISLAY SETTINGS PAGE
Parameter Name
Description
Default Setting
Backlight
It defines whether the back light remains ON or turns OFF
Stand-By ON
during Standby
Homepage
It defines which page to show at power up or pressing the
Main Menu
“Home” shortcut button
Service Password
Password required to enter settings page
0
User Password
Password Required to change locked values
0
(All values are locked by default)
Stand By
It defines the behaviour of the display once the “Stand By Timer”
-
has expired without interactions from the user
Stand By Timer
It defines the inactivity period, in minutes, required to force
0 min
the display in Stand By mode and for both Service and User
passwords expiration. Defining this parameter to Zero, the
passwords request (if any) is prompted at any access to pages
requiring them
Feedback Sound
It defines whether the device shall provide a sound feedback
OFF
during user interaction
Alarm
It defines whether the device shall provide a sound feedback
OFF
when receiving a new Alarm. The notification sound can be
continuous (ON) or intermittent (BEEP)
Date
It adjusts settings related to the Day, Month and Year of the
FAD integrated clock
Time
It adjusts settings related to the Hour and Minute of the
FAD integrated clock
Day Of Week
It adjusts settings related to the Day of Week (1-7) of the
FAD integrated clock
9.0 FC BUS DEVICES
30. 11. 15. Leaflet Number 671710
9.6 SETTINGS PAGES
These set of pages allow the user to configure the technical functions of
the LCD both from the BACnet and user interface perspectives.
The settings page requires a service password for access.
9.6.1 NETWORK SETTINGS PAGE
Allow the user to discover all devices connected on the MS/TP network and
browse all objects exposed within these devices.
Summary of Contents for ecosmart CONNECT XBOXER XBC
Page 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Page 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...