23
nuaire.co.uk
XBOXER XBC
ECOSMART (CO) MODELS
7.15 EXPOSED BACNET OBJECT LIST (BY CATEGORY)
ALARM
LCD Browser
BACnet Object
Description
Object
Object ID
Default Value
Units
Page
Type
20
Fault Relay Cmd
The state of the fault relay
BO
10188
N/A
Alarm/Normal
(Fault = De-energised)
9
Alarm Delay
Alarm hold off period
AV
10262
10
Seconds
22
Reset Alarms
Changing this value will reset any
BV
10332
FALSE
True/False
latched alarms
19
Alarm Circuit 1
The state of Alarm Circuit 1
BI
10167
N/A
Normal/Alarm
19
Alarm Circuit 2
The state of Alarm Circuit 2
BI
10170
N/A
Normal/Alarm
12
High Temp Alarm
Supply temp which will trip the
AV
10277
50
Degrees-Celsius
high supply alarm
13
Low Temp Alarm
Supply temp which will trip the
AV
10280
8
Degrees-Celsius
low supply alarm
30
Low Temp Action
Action taken when the low supply
MSV
10211
Alarm Only
Alarm only / Alarm and
alarm is engaged
stop fans
35
Critical Alarm
Unit is latched in critical alarm
MSV
15309
N/A
Normal/Alarm
36
Maint. Alarm
Maintenance Alarm
MSV
15310
N/A
Normal/Alarm
36
XBC Sensor Alarm
XBC Sensor Out of Range
MSV
17009
N/A
Normal/Alarm
37
Low SA-T Alarm
Low Supply Air Alarm
MSV
17011
N/A
Normal/Alarm
37
High SA-T Alarm
High Supply Air Alarm
MSV
17012
N/A
Normal/Alarm
37
Frost Alarm
The unit is in frost mode
MSV
17013
N/A
Normal/Alarm
LCD EVENT SIGNAL
37
Ala(A Circ 1)
For LCD Event Signal only
MSV
17281
N/A
Normal/Alarm
38
Nor(A Circ 1)
For LCD Event Signal only
MSV
17282
N/A
Normal/Alarm
38
Ala(Low Supply Temp)
For LCD Event Signal only
MSV
17285
N/A
Normal/Alarm
38
Nor(Low Supply Temp)
For LCD Event Signal only
MSV
17286
N/A
Normal/Alarm
38
Nor(High Supply Temp) For LCD Event Signal only
MSV
17289
N/A
Normal/Alarm
39
Ala(High Supply Temp)
For LCD Event Signal only
MSV
17290
N/A
Normal/Alarm
39
Ala(A Circ 2)
For LCD Event Signal only
MSV
17293
N/A
Normal/Alarm
39
Nor(A Circ 2)
For LCD Event Signal only
MSV
17294
N/A
Normal/Alarm
39
Ala(Frost)
For LCD Event Signal only
MSV
17316
N/A
Normal/Alarm
40
Nor(Frost)
For LCD Event Signal only
MSV
17317
N/A
Normal/Alarm
40
Ala(XBC Sensor)
For LCD Event Signal only
MSV
17320
N/A
Normal/Alarm
40
Nor(XBC Sensor)
For LCD Event Signal only
MSV
17321
N/A
Normal/Alarm
7.0 DESCRIPTION OF CONTROL SOFTWARE STRATEGY
30. 11. 15. Leaflet Number 671710
FACTORY SETTINGS
28
Damper Override
Override bypass damper position
MSV
10204
Auto
Auto/Heat Exchange/Bypass
33
Tacho PCB Fitted
Is a “Taco Bell” PCB fitted
MSV
10244
As per build
Yes/No
22
Tuning Reset
Resets the PID auto tuning loops
BV
12880
FALSE
True/False
29
Ignore PIR Sensors
Ignore all MSTP network PIR sensors
MSV
10208
No
Yes/No
18
EF Max Volt
The upper voltage for the extract fan
AV
17273
10
volts
18
EF Start Volt
The voltage required to start the
AV
17274
1
volts
extract fan
18
SF Max Volt
The upper voltage for the supply fan
AV
17275
10
volts
18
SF Start Volt
The voltage required to start
AV
17276
1
volts
the extract fan
40
SW-FAC2612-2-4A
Strategy Version
MSV
17340
Off
Off/On
Summary of Contents for ecosmart CONNECT XBOXER XBC
Page 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Page 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...