29
Heating Type
Set the type of heating fitted
MSV
10206
None/LPHW/Electric
As per
Build
29
H Sensor Op
Humidity Sensor Operation
MSV
10207
Average CO2/Max CO2
Average
/Ignore Humidity
RH%
29
Ignore PIR
Sensors Ignore all MSTP network PIR sensors
MSV
10208
Yes/No
No
29
IN4 Function
Function of the UI4 input
MSV
10209
None/Fan Speed Control
None
EGG
0-10V CO2 Sensor
0-10V Temperature Sensor
0-10V Humidity Sensor
0-10V Pressure Sensor
30
IN5 Function
Function of the UI5 input
MSV
10210
None/Fan Speed Control
None
EGG
0-10V CO2 Sensor
0-10V Temperature Sensor
0-10V Humidity Sensor
0-10V Pressure Sensor
30
Low Temp Action
Action taken when the low supply alarm is engaged MSV
10211
Alarm only/Alarm and
Alarm Only
stop fans Alarm Only
30
0-10V Press. Range
Pressure sensor range
MSV
10212
0-25Pa/0-50Pa /0-100Pa
/0-300Pa /0-500Pa /0-1000Pa
/0-1600Pa /0-2500Pa
/0-3000Pa 0 to 1000Pa
30
P sens. Op
Pressure sensor operation
MSV
10213
Average Value /Max Value
Average
Value
31
SetPoint Op
Setpoint operation
MSV
10214
Last Value Changed
Last Value
/Software Only
Changed
31
T Sens. Op
Temperature sensor operation
MSV
10215
NS Average/Return Air Only
NS Average
/NS & Return Average
31
0-10V Temp Range
Temperature sensor range
MSV
10216
0 to 50°C /0 to 40°C
0 to 50°C
/0 to 100°C /0 to 80°C
/0 to 90°C
31
Auto Run-on
Auto-run on mode
MSV
10217
Off/On
Off
32
Enable
Software enable switch
MSV
10218
Off/On
Off
32
Enable via Schedule
Enabled via Schedule
MSV
10219
Off/On
N/A
32
Fan Boost
Software enabled Fan boost
MSV
10240
Off/On
Off
32
Hibernate Mode
Unit is ready for hibernation
MSV
10241
Off/On
Off
33
Night C Mode
This input will enable night cool mode
MSV
10242
Off/On
Off
33
Purge Active
This input will enable purge mode
MSV
10243
Off/On
Off
33
Tacho PCB Fitted
Is a “Taco Bell” PCB fitted
MSV
10244
Yes/No
As per
Build
33
Temp Control Mode
Temperature control mode
MSV
10245
Supply Temperature Ctrl
Supply
/Return Temperature Ctrl
Temp.
Control
34
Test (Fan)
Fan Test (Factory Use Only)
MSV
10246
Off/On
N/A
34
Test (Heater)
Heater Test (Factory Use Only)
MSV
10247
Off/On
N/A
34
Test (Override Fan)
Overtemp Test (Factory Use Only)
MSV
10248
Off/On
N/A
34
Test (Wiring)
Wiring Test (Factory Use Only)
MSV
10249
Off/On
N/A
30. 11. 15. Leaflet Number 671710
Summary of Contents for ecosmart CONNECT XBOXER XBC
Page 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Page 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...