029 2085 8200
20
XBOXER XBC
ECOSMART (CO) MODELS
7.0 DESCRIPTION OF CONTROL SOFTWARE STRATEGY
TEMPERATURE CONTROL
15
Software Setpoint
Software Setpoint
AV
10309
22
Degrees-Celsius
10
Deadband
Deadband for temp control
AV
10266
3
Degrees-Celsius
31
SetPoint Op
Setpoint operation
MSV
10214
Last Value Chg
Last Value Changed
/Software Only
31
T Sens. Op
Temperature sensor operation
MSV
10215
NS Average
NS Average/Return Air Only/
NS & Return Average
31
0-10V Temp Range
Temperature sensor range
MSV
10216
0 to 50°C
0 to 50°C/0 to 40°C/
0 to 100°C/0 to 80°C/
0 to 90°C
33
Temp Control Mode
Temperature control mode STC/RTC
MSV
10245
ReturnTempCtrl Supply Temperature Ctrl/
Return Temperature Ctrl
15
STC H/C Pref
STC Heat/Cool Pref
AV
10310
50
No units
16
STC HX Efficiency
STC HX Efficiency
AV
10311
0.8
No units
14
RTC Boost Band
Return Temperature Control Boost Band
AV
10306
15
Degrees-Celsius
15
RTC Max Supply Temp Max supply temp when in RTC mode
AV
10307
35
Degrees-Celsius
15
RTC Min Supply Temp Min supply temp when in RTC mode
AV
10308
12
Degrees-Celsius
7.15 EXPOSED BACNET OBJECT LIST (BY CATEGORY)
FAN COMMISSIONING
LCD Browser
BACnet Object
Description
Oject
Object ID
Default Value
Units
Page
Type
10
Extract Fan Max
Individual fan maximum speed setting
AV
10268
100
Percent
11
Extract Fan Min
Individual fan minimum speed setting
AV
10270
20
Percent
16
Supply Fan Max
Individual fan maximum speed setting
AV
10312
100
Percent
16
Supply Fan Min
Individual fan minimum speed setting
AV
10314
20
Percent
HEATING OUTPUT
29
Heating Type
Set the type of heating fitted
MSV
10206
As per build
None/LPHW/Electric
7
Heating Output
The 0-10V signal to the heating output
AO
10179
N/A
Percent
21
Heating Demand Cmd The state of the heating demand relay
BO
10197
N/A
Off/On
COOLING OUTPUT
28
Cooling Type
Set the type of cooling fitted
MSV
10203
None
None/Cold Water/DX
7
Cooling Output
The 0-10V signal to the cooling output
AO
10173
N/A
Percent
20
Cooling Demand Cmd The state of the cooling demand relay
BO
10194
N/A
Off/On
HX BYPASS DAMPER
20
Bypass Damper Cmd The signal to the bypass damper
BO
10185
N/A
Open/Close
(Close = Bypass)
(MS/TP)
Summary of Contents for ecosmart CONNECT XBOXER XBC
Page 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Page 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...