ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
37
997-263, Issue 4
September 2002
5.4Level 3 Configuration Options
The Level 3 Configuration Options allow you to configure
the panel. These Options are listed in the menu map at
left. The default Level 3 passcode is given in
Appendix 1 -
Specifications
.
Before any configuration changes can be made, the memory
lock must be set to the unlocked position (see below).
Memory Lock Jumper Link
Jumper link MEM (J9) locks/unlocks the system
configuration. J9 is located to the left of the Digital / ÜE
terminal block (TB8). To configure the panel, J9 must be
in the unlocked position (link NOT fitted).
Fit the link to the jumper (J9) before returning to
normal operation.
Any attempt to access a configuration menu option while
the link is fitted will cause the following message to be
briefly displayed:
Memory is Locked!
J9
MEM
J9
MEM
LOCKED
UNLOCKED