ID50 Series Panel - Installation, Commissioning & Configuration Manual
Commissioning
33
997-263, Issue 4
September 2002
4.6 Configuration and Handover
After all external wiring has been connected to the panel
and with the LCD displaying the Status: NORMAL
message, the panel can be configured for the particular
system requirements. Refer to
Section 5, Configuration
.
After configuration has been completed and any faults
revealed have been rectified, the system will be ready
for commissioning tests (see
Section 4.7,
Commissioning Tests
), as required by the appropriate
standards, prior to handover to the user.
Panel configuration is performed via the Commission
menu:
1
When the Status: NORMAL message is displayed,
press the
button. The LCD prompts for entry of
an access code as displayed below:
2
Either turn the keyswitch or, using the numeric keypad
(see
997-264, ID50 Series Panel - Operating Manual,
Section 4.6, Numeric Keys
), enter either the:
a. Level 2 access code, or
b. Level 3 access code.
Refer to
Appendix 1 - Specifications
for the default
passcodes.
If the correct Level 2 access code (User) is entered,
the Access Level 2 Menu and a user number (U0 - U9)
is displayed in the top left-hand corner of the LCD
(this is always U9 if the keyswitch is used):
or if the Level 3 access code (Service) is correctly
entered, the LCD displays [S1] in the top left-hand
corner:
If an incorrect access code is entered, the LCD displays
a message:
To return to the normal quiescent state, press the
4
button.
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . .
< : BackSp
[U0] 1:Test
2:Disable/Enable
3:Clock
4:View Mode
5:Commission
[S1] 1:Test
2:Disable/Enable
3:Clock
4:View Mode
5:Commission
ERROR - INCORRECT PASSCODE ! ! !
1
2