ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
71
997-263, Issue 4
September 2002
5.7.9 Device Inputs
The Device Inputs option is only available if the Device
Inputs CBE Rule is selected. This option determines the
output response to up to three (3) specified input devices
(modules or sensors). An input from any of the specified
devices will turn on the associated outputs.
To select the input devices:
1
Follow the procedures in
Section 5.7.1, CBE Rules:
Output Type
to change the CBE Rule type to Inputs.
The LCD displays the following menu:
2
Using the numeric keypad press the
1
button to
display the following menu:
3
At the numeric keypad press the
0
button to select
the Devices option. The LCD then prompts for a
device type selection (sensor or module) or the
removal of a device that has already been entered.
Alternatively press the
4
button to exit this menu.
4
Use the
2
/
8
buttons to select one of the 3 Device
Inputs to be edited.
5
Select either
1
(sensor) or
2
(module) to select
device address entry, or
3
to remove the currently
selected device. If a device is to be entered, the
following (example is for a sensor) is displayed:
6
At the numeric keypad, enter the device address and
press the
5
button to confirm. Alternatively press
4
repeatedly to cancel the address entry.
CBE 09 [INPUTS ]
Dv1 Dv2 Dv3
1 : Change[EvSl
]
---
---
---
CBE Rule:09
1:Type
2:Evac
4:Silence
6:Class Change
10:Devices
CBE Rule 09
Device 1: ---
1:Sensor 2:Module
3:Remove
<: Exit
CBE Rule 09
Device n: Snn
1:Sensor 2:Module
3:Remove
<: Exit
CBE Rule 09
Device n: ---
Enter sensor address
<: Cancel
CBE Rule 09
Device n: Snn
1:Sensor 2:Module
3:Remove
<: Exit
or
1
2
8
or
2
or
3
1
0