AVS Group
The AVSGroup option is used to associate a number of
either AVS or AVR sensors in up to a maximum of 50
groups, see
Section Co-operative Multi-Sensing
. The
operation of VIEW
TM
sensors assigned to a group is as
follows:
a. VIEW
TM
sensors operate independently if the sensor
is assigned to group 0.
b. In a group containing both types, the AVSs desensitise
if AVRs detect a sudden rise in contaminated air.
c. In a group containing AVS type sensors, all sensors
operate as standard VIEW
TM
sensors.
Note:
One or more AVRs may be configured in a group.
To assign a sensor to a group:
1
From the VIEW
TM
sensor Sensitivity menu, using the
numeric keypad press
3
to access the AVSGroup
option.
2
The LCD prompts for a new AVS Group number. Use
the numeric keypad to enter the required group
number and press
5
to confirm.
3
The LCD then returns to the previous display.
A2.4 Automatically Learning VIEW
TM
Sensors
When automatically learning an SLC Loop including
VIEW
TM
sensors, each sensor is configured as an AVS
type. The LCD shows the total number of these sensors,
as in the example below:
Any sensors that need to be configured to an AVR type
must be changed individually, see
Section A2.2,
Learning Individual VIEW
TM
Sensors
.
[Sensor nn - AVS]
Sensitivity
1 : Alarm(L5,5) 2 : Day(L5,5) 3 : AVSGroup(01)
[Learn] TOTAL ION OPT TMP MLT AVS
68
10
20
25
05
08
[Sensor nn - AVS]
Sensitivity
Enter new AVS Group : ____
< : Cancel
[Sensor nn - AVS]
Sensitivity
1 : Alarm(L5,5) 2 : Day(L5,5) 3 : AVSGroup(01)
3