ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
64
997-263, Issue 4
September 2002
(P)ulsed - the zone is included in the CBE Rule. An
alarm in this zone will activate outputs immediately in
pulsed mode. This mode is overridden if an alarm
occurs in any zone that is included in this rule and for
which Pulse Mode is not selected, also if a device is
assigned to multiple CBE rules and a rule for which
Pulse Mode is not selected becomes active.
ii Zones 17 to 32 - addresses the plant warning rule
silence options. These zones can be configured in
the same manner as described for zones 01 to 16.
h.
Soak Timer (Sk Tmr)
- has two options Yes (Y) or No
(N). If set to Y(es) the associated extinguishing output
is active only for the time specified in the System Soak
Timer Setup menu.
To select the CBE Rule menu, proceed as follows:
1
With the Commissioning menu displayed, press the
3
button on the numeric keypad.
2
The LCD prompts you to enter a CBE Rule number
as shown below:
Enter the required CBE Rule number using the
numeric keypad and confirm by pressing the
5
button.
3
The LCD then displays the selected CBE Rules
current configuration and a menu option to allow
changes to the rule. The displayed configurable
options depend upon the rule type. To change the rule
configuration press the
1
button on the numeric
keypad.
Note:
You can use the
2
/
8
buttons to step through
each of the 64 CBE Rules.
4
At the menu below, use the numeric keypad to select
the option that requires changing.
Note:
Selectable options are dependent upon the type
of the current CBE Rule.
[S1 COMM] 1 : Setup
2 : Circuit
3 : CBE Rules
4 : Zones 5 : Access
×
: More
CBE 01 [FIRE
][ANY] 1--------------------16
1 : Change[EvSlln
] YYYYNNYYNDDNCCNN
[CBE Rule]
Select Rule No ____
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
×
: More
CBE Rule:01
6:Class Change
7:Two Zone
9:Zones
×
: More
3
1