ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
49
997-263, Issue 4
September 2002
5.5.20 Weekend Night Mode
If Weekend night mode is enabled, the panel disregards
the Day mode period on the two days of the week that
coincide with the weekend. To set this mode active:
1
From the Commissioning menu, using the numeric
keypad press the
1
button to enter the Setup menu.
2
Press the
2
/
8
buttons to step through the Setup
menus until the Weekend night mode menu is displayed.
3
Press the
6
button to toggle this function.
4
Press
4
to exit and return to the Commissioning
menu.
5.5.21 Auto High Test
The Auto High Test setup menu configures the panel to
test each device on the loop at a specified time. The test
checks that each device is able to produce an alarm
reading at the panel. To configure the Auto High Test:
1
From the Commissioning menu, using the numeric
keypad press the
1
button to enter the Setup menu.
2
Press the
2
/
8
buttons to step through the Setup
menu until the Auto High Test menu is displayed.
3
Press the
6
button to enter (edit) the time at which
Auto High Test will start.
4
Using the numeric keypad, enter an appropriate start
time in the 24-hour clock format and confirm the set
time using the
5
button. The LCD automatically
returns to the Auto High Test menu. Alternatively, press
4
to cancel all changes and return to the Auto High
Test menu.
[Setup]
Weekend night mode = Disable
> : Change
×
: More
< : Exit
[Setup]
Weekend night mode = Enable
> : Change
×
: More
< : Exit
[Setup]
Auto High Test = DISABLED
> : Change
1 : Disable
×
: More
< : Exit
[Setup]
Auto High Test = DISABLED
Enter start time :
-0:00
< : Cancel
[Setup]
Auto High Test = DISABLED
> : Change
1 : Disable
×
: More
< : Exit
[Setup]
Auto High Test = 07:46
> : Change
1 : Disable
×
: More
< : Exit
[Setup] Language =
English
> : Change
×
: More
< : Exit
[Setup] Language =
English
> : Change
×
: More
< : Exit
1
or
8
2
6
1
or
8
2
6
5
4