OWN-ADV 01/12
9.3 REGISTER MAP (CONT’D)
40003 -
40010
(Read
Only)
Each event uses 5bits,
b4, b3, b2, b1, b0 where b0 is the least signi
fi
cant bit.
b0 = The event status (warning or shutdown occurring)
0 = Not Active, 1 = Active
b2-b1 = The severity of the event
0 = Take No Action, 1 = Warning/Acknowledge
2 = Action Required, 3 = Take Immediate Action (shutdown)
b3 = Alarm Action (indicates if WaveNet is sounding buzzer)
0 = No Audible Alarm, 1 = Sound Audible Alarm
b4 = Warning/Failure Feature Enabled/Disabled
0 = Disabled, 1 = Enabled
40003
Events number 1 System Ready bit 4-0
Events number 2 Over crank bit 9-5
Events number 3 High Engine Temperature Warning / Shutdown bit 14-10
40004
Events number 4 Low Oil Pressure Warning / Shutdown bit 4-0
Events number 5 Over speed bit 9-5
Events number 6 Emergency Stop bit 14-10
40005
Events number 7 Low Coolant Level bit 4-0
Events number 8 Low Coolant Temperature bit 9-5
Events number 9 Low Fuel Level In Tank bit 14-10
40006
Events number 10 Low Fuel Pressure bit 4-0
Events number 11 Emergency Power Supplying Load bit 9-5
Events number 12 Generator Running bit 14-10
40007
Events number 13 Generator Not In Auto Mode bit 4-0
Events number 14 Battery Charger Fault bit 9-5
Events number 15 Battery Voltage Low bit 14-10
40008
Events number 16 Battery Voltage High bit 4-0
Events number 17 Low Battery Voltage During Cranking bit 9-5
Events number 18 Locked Rotor bit 14-10
40009
Events number 19 Common Fault #1 Warning/Shutdown bit 4-0
Events number 20 Common Fault #2 Warning/Shutdown bit 9-5
Events number 21 Reserved bit 14-10
40010
Reserved