OWN-ADV 01/12
40083
bit0: Battery low and high level warning
bit1: Not used
bit2: Low coolant level failure
bit3 : Controller is not in auto
bit4: Failure has occurred
bit5 : Cranking rest active
bit6: Controller is in RUN mode
(after crank success)
bit7: Controller is cranking
bit10: AC under voltage warning
bit11: AC over voltage warning
bit12: AC over current warning
bit13: Fuel in basin warning
bit14: Voltage Regulator Digital Output
feature is on.
bit15: Low engine temperature warning
40084
bit0: Backlight is on
bit1: Auxiliary warning
bit2 : Maintenance is required
bit3: System is OK (de
fi
nition: no
warning, including not in auto
warning)
bit4: Common fault 1 digital output
feature (warning and failure)
bit5: Common fault 2 digital output
feature (warning and failure)
bit6: Dummy load digital output feature
bit7 : reserved
bit8 : Over current latch (AC Current
feature)
bit9: User con
fi
gurable warning 1 digital
output feature
bit10: User con
fi
gurable warning 2
digital output feature
bit11: User con
fi
gurable failure1 digital
output feature
bit12: User con
fi
gurable failure 2 digital
output feature
bit13 to bit15: (Reserved)
9.3 REGISTER MAP (CONT’D)