OWN-ADV 01/12
Some industry standard failures, warnings, and events
on the WaveNet are indicated by a series of LEDs on the
left side of the controller.
Speci
fi
c LED indicators will be illuminated depending
upon the condition of the controller. The WaveNet LED
indicators allow a quick check of the controller’s condition.
The WaveNet displays multi color LED’s for speci
fi
c
condition representation.
Red
- Represents Failure Conditions
Yellow
- Represents Warning Conditions
Green
- Represents Normal/Active Conditions
An LED test may be performed by the
user for illumination of all controller
LED’s. The LED test may be
performed
by simultaneously pressing
the Up key and the Down key on the
WaveNet.
4.10 WAVENET LED STATUS INDICATORS
Table 7: WaveNet Lamp Indication Meanings
LED
Description
LED color
LED Status
Indication
Over Crank
Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents an Over Crank
condition on the
fi
nal crank attempt. This is a Failure.
A solid yellow illuminated LED represents an Over
Crank Warning condition when there are crank attempts
still remaining.
High Engine
Temp
Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents a High engine
Temp Failure condition
A solid yellow illuminated LED represents a High engine
Temp Warning Condition
Low Oil
Press
Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents a Low Oil
Pressure Failure condition.
A solid yellow illuminated LED represents a Low Oil
Pressure Warning condition.
4.11 LAMP INDICATION MEANINGS