OWN-ADV 01/12
Over Voltage Warning
This turns on the digital output when the AC Over Voltage Warning is
activated
(Section 5.3.2)
.
Over Current Warning
This turns on the digital output when the AC Over Current Warning is
activated
(Section 5.3.3).
Fuel in Basin Warning
This turns on the digital output if the Low Fuel In Basin Warning
(
section 5.1
) is activated.
Low Temp Warning
This turns on the digital output if the Low Engine Temperature Warning
(section 5.1
) is activated.
Backlight
This turns off the digital output if the LCD backlighting turns off.
The controller enters the sleep mode (
section 4.4
) when this
occurs.
Auxiliary Warning
This turns on the output if the Auxiliary Warning Digital Input
(see
Table 13 in section 5.6
) is active.
Maintenance Timer
This turns on the output if maintenance is required to be performed on
the engine/generator. See
section 5.9
.
System Ready
This turns on the output if the controller is in the auto state with no
warnings (some warnings are ignored for this feature such as low and
high battery voltage).
Common Fault Output 1
This turns on the output if the Common Fault 1 feature is active. See
section 5.11
for more details.
Common Fault Output 2
This turns on the output if the Common Fault 2 feature is active. See
section 5.11
for more details.
Dummy Load
This allows the digital output to be controlled by the Dummy Load feature.
See
section 5.12
for more details.
High Fuel Level Warning
This turns on the output if the High Fuel Level Warning digital
input in
Table 13 on page 38
is active.
Current Latch
This turns on the output if the Cur Warn Latch in the AC Current menu (see Table 9
on page 24) is set to Enable and the High Current Warning is active. The output can
only be turned off by the user. See
Section 5.3.2 on page 31
for more information.
Con
fi
g Warn 1
This turns on the output if the Con
fi
g Warn 1 digital input (Table 13 on page 38) is active.
Con
fi
g Warn 2
This turns on the output if the Con
fi
g Warn 2 digital input (Table 13 on page 38) is active.
Con
fi
g Fail 1
This turns on the output if the Con
fi
g Fail 1 digital input (Table 13 on page 38) is active.
Con
fi
g Fail 2
This turns on the output if the Con
fi
g Fail 2 digital input (Table 13 on page 38) is active.
5.5 DIGITAL OUTPUT SETUP (CONT’D)
37