OWN-ADV 01/12
Table 7: WaveNet Lamp Indication Meanings (cont’d)
LED
Description
LED color
LED Status
Indication
Over
Speed
Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents an Over Speed
Failure condition.
A solid yellow illuminated LED represents an Over
Speed Warning condition.
Battery
Status
Green
Yellow
Solid Green
Flashing
Green
Solid Yellow
A solid green illuminated LED represents a normal battery
condition.
Controller in Auto mode - Waiting to start
A solid yellow illuminated LED represents a Low Battery
condition.
Low
Coolant
Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents a Low Coolant
(Temperature and/or Level) failure condition
A solid yellow illuminated LED presents a Low Coolant
Temperature Warning condition.
Pre-Heat
Green
Solid Green
A solid green illuminated LED represents an active Pre-Heat
condition
Genset
Online
Green
Red
Solid Green
Solid Red
A solid green illuminated LED indicates that the generator
is supplying load and is operating normally.
A solid red indicated load is detected on the generator
when none should be.
See section 4.13 on page 22 for more information
about the EPS Supplying Load.
Failure
Red
Solid Red
A solid red illuminated LED represents a general Failure
condition.
4.11 LAMP INDICATION MEANINGS (CONT’D)
The WaveNet incorporates many types of warnings and failures. Some are only active in the RUN mode
while others are also active in the AUTO and/or OFF modes. Warnings and failures can be triggered
from a Digital Input, Analog Input, AC Voltage, AC Current, Speed Signal Input, as well as others. The
Advanced Setup section of this manual will give more information of the speci
fi
c warning and failures for
each type of input.
When a
warning
occurs, the second line (the area under the time and date display) of the LCD is used to
display the warning text. Also, after the warning is displayed, instructions are displayed showing the user
how to silence the warning. When in the AUTO or RUN modes the instructions are to press the Info key
and when in the OFF mode press the Stop key.
4.12 WARNINGS AND FAILURES
21
Summary of Contents for OWN-ADV
Page 71: ...69 THIS PAGE INTENTIONALLY BLANK...
Page 72: ...11 APPENDIX D ADDITIONAL DRAWINGS OWN ADV 01 12...
Page 73: ......
Page 74: ...THIS PAGE INTENTIONALLY BLANK...
Page 88: ...OWN ADV 01 12 84 WAVENET REMOTE PANEL INSTALLATION DIMENSIONS B 9829...
Page 89: ......
Page 90: ......