OWN-ADV 01/12
10.1 NORTHERN LIGHTS PROPRIETARY (FAST PACKET)
66
Start Position (Byte)
Data Length Parameter Name
Description
9
1 byte
Genset controller
failure code
18 Loss Of ECM (Failure)
19 EPS Supplying Load (Failure)
20 User Text 1 (Failure)
21 User Text 2 (Failure)
0 No Failure
10
2 bytes
Trip Running Time
Generator run time since last start.
Resets to zero when generator stopped
Resolution 1 bit = 6 minutes
12
1 byte
Genset Controller
Parameters Setting
Bit0~1: AC Voltage
0 = AC not ready
1 = Single Phase 1 Wire
2 = Single Phase 2 Wire
3 = 3 Phases
Bit 2~3: Engine Temperature
3 = Sender
2,1 = Switch
0 = Not Available
Bit4~5: Fuel Level
3 = Sender
2,1 = Switch
0 = Not Available
Bit6~7: Oil Pressure
3 = Sender
2,1 = Switch
0 = Not Available
Bit8~15: (Reserved)
14
4 bytes
Genset Controller
LED Status
bit0: Over Crank Failure (red)
bit1: Over Crank Warning (amber)
bit2: High Engine Temp Failure (red)
bit3: High Engine Temp Warning (amber)
bit4: Low Oil Pressure Failure (red)
bit5: Low Oil Pressure Warning (amber)
bit6: Engine Over Speed Failure (red)
bit7: Engine Over Speed Warning (amber)
bit8: Low Fuel Level Failure (red)
bit9: Low Fuel Level Warning (amber)
bit10: Low Battery Warning (amber)
bit11: Battery OK (solid green in OFF
and RUN modes,
fl
ashing green in AUTO
mode)
bit12: Not In Auto (red)
bit13: Not Used
bit14: Low Coolant Level Shutdown (red)
bit15: Low Coolant Level Warning (amber)
bit16: EPS Supplying Load Shutdown (red)
bit17: EPS Supplying Load Warning (amber)
bit18: not used
UPDATED 6/24/11
Summary of Contents for OWN-ADV
Page 71: ...69 THIS PAGE INTENTIONALLY BLANK...
Page 72: ...11 APPENDIX D ADDITIONAL DRAWINGS OWN ADV 01 12...
Page 73: ......
Page 74: ...THIS PAGE INTENTIONALLY BLANK...
Page 88: ...OWN ADV 01 12 84 WAVENET REMOTE PANEL INSTALLATION DIMENSIONS B 9829...
Page 89: ......
Page 90: ......