OWN-ADV 01/12
When a
failure
occurs (although most failures only occur in the RUN mode, the
Low Fuel Level and
Low Coolant Level
failures occur in any state including OFF and AUTO) the controller exits the RUN
mode and goes to the FAILURE mode – turning off the Fuel output and other outputs on or off depending
on the advanced settings – and displays the failure message. The alarm will sound and remain on until
it is silenced by the user. The Info key can be pressed to silence the alarm. Once the alarm is silenced it
can be reset by pressing the Info key and then the Stop key. This returns the controller to the OFF mode.
The failure is recorded in the event log accessible from the Basic Menu.
4.12 WARNINGS AND FAILURES (CONT’D)
When the generator is started and load is detected on the generator when the WaveNet is in the RUN
mode the
“Genset Online”
LED on the WaveNet front panel will turn green. This indicates that the
generator is supply load as normal. If load is detected on the generator when it is not in the RUN mode
(e.g. the WaveNet is cranking, preheating, etc.) the WaveNet terminates starting and enters the FAIL-
URE mode and the “Genset Online” LED on the WaveNet front panel will turn red.
The generator is considered loaded when either the AC current is equal to or greater than 5% of the over
current failure set point or if the EPS Supplying Load Switched Input is active.
The WaveNet incorporates an Advanced Setup menu. The possible
advanced menu selections are covered in this section. Only
advanced and knowledgeable users should change these parameters.
Before entering the Advanced menu a password is required to be
entered. The password will consist of a four digit number. Each
number needs to be selected using the up or down arrows on the
WaveNet. Simply choose the correct password number for each
selected position by scrolling to the proper number followed
by the Enter key. The default password is 0 0 0 0.
The password may be changed anytime. See Password Setup section.
The Advanced Setup menu on the WaveNet is shown to the right.
4.13 GENSET ONLINE
5. ADVANCED SETUP
22
Summary of Contents for OWN-ADV
Page 71: ...69 THIS PAGE INTENTIONALLY BLANK...
Page 72: ...11 APPENDIX D ADDITIONAL DRAWINGS OWN ADV 01 12...
Page 73: ......
Page 74: ...THIS PAGE INTENTIONALLY BLANK...
Page 88: ...OWN ADV 01 12 84 WAVENET REMOTE PANEL INSTALLATION DIMENSIONS B 9829...
Page 89: ......
Page 90: ......