OWN-ADV 01/12
43
RUN
- The local WaveNet panel is running and the genset can be stopped from any enlisted WaveNet
Remote by pressing the Stop key. This state includes some sub-states like “Cranking, Preheat, Warm-Up,
Running, Idle-Running, Cooling Down,etc.” The detail sub-state messages will show on the second line of
the LCD display.
FAIL
- The local WaveNet panel has shutdown and is in FAILURE mode. The failure must be cleared at
the local WaveNet panel before the generator can be restarted.
OFF
- The local WaveNet panel is in the OFF state and therefore cannot be started from a WaveNet
Remote panel.
MENU -
The local WaveNet panel is in the menu settings or off sleep state.
7.1.2 STATE (CONT’D)
updated 1-20-12
The Status Mark indicates the on-line genset’s control status. An “x” Status Mark to the right of
the generator’s description indicates an un-enlisted genset, only monitoring is enabled on these
gensets. A “
” Status Mark indicates an enlisted generator, which has start and stop control
enabled in addition to monitoring. Note that even with an enlisted Remote panel the local genset
controller must be in the Auto mode to be started remotely.
7.1.3 STATUS MARK
The ON-LINE GENSET PARAMETER mode has 3 different pages corresponding to the on-line genset
controller, the AUTO, RUN and FAIL states. Start and stop functionality is the same in this mode as the
ON-LINE GENSET STATUS mode. Press the Info key to return to the ON-LINE GENSET STATUS mode.
7.2 ON-LINE GENSET PARAMETER MODE
AUTO
- Displays 4 parameters: the engine
temperature, engine hours, battery voltage and
local WaveNet Remote unit board temperature.
RUN
- Displays all selected genset running
parameters like engine speed, engine temperature,
AC voltage current, etc. The display area will cycle
to display the different parameters. Operation here
is the same as the local WaveNet panel.
FAIL
- Displays current active failures that caused
the genset shutdown.
Note: the remote display will switch automatically according to current selected genset controller
state. For example, remote unit is displaying AUTO parameters page, if the selected genset goes
into running, the remote unit display will switch to display RUN parameters page. If genset was in
shutdown state due to some failure happen or user shutdown, the remote unit will switch back to
on-line genset status page.