Installation | 22
External Controls
Control Wiring
The following information is relevant to all controls, factory supplied or otherwise. For wiring use
a minimum of 18 AWG and keep as short as possible. The NHRS humidifier can be operated
with a modulating input or as On/Off.
Control Location
Figure 13: Control Location (Duct Humidification)
Duct Humidification
1
Air Proving Switch
Locate so that it can sense air flow, or lack thereof.
2
Duct High Limit
NHRS operates with On/Off control.
Locate at least 10 feet (3.0 m) from steam distributor, or far enough that steam is
fully absorbed under normal conditions.
3
Humidity Control
NHRS can be modulating, On/Off, or a humidity sensor.
Can be located either in return air duct (preferred) or in room being humidified.
Mount in area representative of room humidity (draft, doorways, sunlight, or
overhang such as shelf can affect reading). Avoid placing near discharge diffuser of
humidified air.
4
Outdoor Temperature Sensor
Mount in area representing outdoor air temperature (makeup air duct, outside).
Caution:
Failure to wire the humidifier in accordance with the wiring instructions
could cause permanent damage. Such errors will void the warranty.
Summary of Contents for NHRS 010-090
Page 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Page 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Page 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Page 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Page 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Page 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Page 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Page 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...