37 | Start Up
c.
Check for correct functioning of the monitoring equipment (external safety
network).
d.
Set the desired humidity value on the humidity controller / humidistat.
e.
Make sure no leaks are present.
The heating current switches on as soon as the humidity controller / humidistat
demands humidity. The yellow LED lights and steam is produced after a short delay
(approximately 5 minutes).
2.
The operating status is displayed in the LED on the unit as follows:
Table 8: NHRS Operational Status LEDs
LED
Action
Meaning
Green
Constant
Unit Producing Steam
Yellow
Flashing
Major or Minor Service Due.
Red
Flashing
The Unit is trying to self-correct a problem.
Red
Constant
Insoluble Problem
NOTE:
Relevant data will be displayed on the NHRS LCD display during normal operation and
when in fault
3.
If the humidifier is equipped with the optional Remote Fault Indication, the operating
status will be shown as follows:
Table 9: Remote Fault Indication
Relay
Description
Notes
K1
Steam
(N/O) Normally open
K2
Error
(N/O) Normally open Or (N/C) Normally closed
K3
Service
(N/O) Normally open Or (N/C) Normally closed
K4
Unit On
(N/O) Normally open
Summary of Contents for NHRS 010-090
Page 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Page 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Page 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Page 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Page 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Page 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Page 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Page 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...