13 | Installation
Note:
• Drain water is very hot, do not drain to public sink.
• Use material suitable for 212ºF (100ºC) for drain and condensate lines.
Plumbing
All water supply and drain line connections should be installed in accordance with local
plumbing codes.
Supply water should have pressure between 30 and 80 psi
g
and have a hardness
between 0 and 12 gr/gal. Various types of supply water may be used: soft water, de-
ionized, reverse osmosis, or potable.
Install water shut-off valve and union before humidifier to facilitate servicing.
The drain line should not end in a sink used frequently by personnel, or where plumbing
codes prohibit. Route to a floor drain or equivalent for safety reasons.
Ensure drain line is adequately sized to provide free and easy draining. Ensure air gap is
installed as shown. A restricted drain can cause the boiling tank to become heavily
concentrated with minerals and may result in poor operation or water backing up at the
air gap.
Figure 7: Water Supply and Drain Connection
Summary of Contents for NHRS 010-090
Page 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Page 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Page 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Page 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Page 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Page 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Page 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Page 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...