Installation | 12
Mounting with Keyholes
1.
The NHRS Series humidifier is wall mounted using keyholes located on the back of the
unit cabinetry.
2.
Use #12 x 3” (7.5 cm) screws mounted into 2x4” studs or better. Two screws are
required for units with one tank (NHRS 10 to NHRS 90 lb/hr). Three screws are required
for units with two tanks (NHRS 135 and 180 lb/hr).
3.
Keyholes are spaced 16” (40.6 cm) apart center to center as per UL certification
standard stud spacing dictates. Insert screws into the studs until there is ¼” (0.6 cm) of
screw exposed. Ensure the screws are level to each other.
4.
Raise the unit and place the screws through the keyholes. Make sure the unit is level
before tightening the screws to secure the unit in place.
5.
Place L-shaped brackets on top of the unit, ensuring the holes are in-line with the studs.
Using the appropriate sized wood screw, fasten the L-brackets to the studs, securing the
unit from any upwards motion. See Figure 6.
Figure 6: Mounting with Keyholes; A = B = 16” (40.6 cm)
Note: Use screws longer than 3” (7.5 cm) if drywall or other spacer is present.
Summary of Contents for NHRS 010-090
Page 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Page 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Page 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Page 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Page 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Page 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Page 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Page 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...