Installation | 10
Location
Mount on a suitable wall or vertical surface. Do not sit the unit on the floor to allow
clearances required for plumbing and electrical connections.
Clearance dimensions shown are for reference only and are the minimum required for
maintenance of the humidifier. Consult local and national codes before final location
and installation. Nortec does not accept responsibility for installation code violations.
Install only in areas with ambient temperatures between 41 and 104ºF (5 and 40ºC),
and relative humidity between 5 and 95% (non-condensing).
When possible, install the humidifier below the steam distributor. If mounted above the
steam distributor, take care to provide proper steam line routing and proper condensate
traps.
DO NOT locate the humidifier any further than absolutely necessary from the steam
distributor location as net output will be reduced as a result of heat loss through the
steam line.
When possible, mount the humidifier at a height convenient for servicing.
Figure 5: Mounting Location / Clearance
Note:
Do not mount on hot surfaces, where freezing can occur, vibrating surfaces, or
floor.
Summary of Contents for NHRS 010-090
Page 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Page 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Page 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Page 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Page 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Page 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Page 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Page 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...