23 | Installation
Space Humidification
1
Humidity
Control
(in location
representative
of the space)
1
Humidity
Control
(in location
representative
of the space)
1
Humidity
Control
(in location
representative
of the space)
Figure 14: Control Location (Space Humidification)
1
Humidity Control
NHRS can be modulating, On/Off, or a humidity transducer.
Locate in room being humidified but not in discharge zone of blower pack(s).
Mount on indoor wall in area representative of room humidity (draft, doorways,
sunlight, or overhang such as shelf can affect reading).
2
High Limit Humidistat (not shown)
Install a high limit On/Off humidistat in area representative of room humidity.
3
Outdoor Temperature Sensor (not shown)
Mount outside in area representing outdoor air temperature.
Note:
Regardless of selecting on/off or modulating control method, Nortec humidifiers must have a
closed circuit across its security loop control terminal to operate. Nortec highly recommends the use
of a high limit humidistat and an air proving switch in series for this function.
Summary of Contents for NHRS 010-090
Page 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Page 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Page 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Page 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Page 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Page 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Page 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Page 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...