background image

2

 – English

English

• 

Before intervening on the system (maintenance, cleaning), always dis-

connect the product from the mains power supply

• 

Check the system periodically, in particular all cables, springs and sup-

ports to detect possible imbalances, signs of wear or damage. Do not 

use if repairs or adjustments are necessary, because a failure with the 

installation or an incorrectly balanced automated system may lead to 

injury

• 

The packaging materials of the product must be disposed of in compli-

ance with local regulations

• 

Keep persons away from the gate when it is moved through the control 

elements

• 

When performing a manoeuvre, keep an eye on the automated mech-

anism and keep all bystanders at a safe distance until the movement 

has been completed

• 

Do not operate the automation if anyone is working on it; disconnect 

the power supply before permitting any work to be carried out

INSTALLATION PRECAUTIONS
• 

Prior to installing the drive motor, check that all mechanical compo-

nents are in good working order and properly balanced, and that the 

automation moves correctly

• 

If the gate being automated has a pedestrian door, the system must 

include a control device inhibiting the operation of the motor when the 

pedestrian door is open

• 

Make sure that the controls are kept at a safe distance from moving 

parts, while allowing a good view of these. 

  Unless a selector is used, the controls should be installed at least 1.5 

m from the ground and must not be accessible 

• 

If the opening movement is controlled by a fire-prevention system, 

make sure that any windows larger than 200 mm are closed by the 

control elements

• 

Prevent and avoid any form of trapping between the moving and fixed 

parts during manoeuvres

• 

Permanently affix the manual operation label next to the element ena-

bling the manoeuvre itself

• 

After installing the drive motor, make sure that the mechanism, protec-

tive system and all manual manoeuvres operate properly

–––  STEP 1  –––

CAUTION - Important safety instructions. Observe all the instruc-

tions as improper installation may cause serious damage
CAUTION - Important safety instructions. It is important to com-

ply with these instructions to ensure personal safety. Store these 

instructions
• 

Before commencing the installation, check the “Product technical 

specifications”, in particular whether this product is suitable for au-

tomating your guided part. Should it be unsuitable, DO NOT proceed 

with the installation

• 

The product cannot be used before it has been commissioned as 

specified in the “Testing and commissioning” chapter

CAUTION - According to the most recent European legislation, the 

implementation of an automation system must comply with the 

harmonised standards set forth in the Machinery Directive in force, 

which allow for declaring the presumed conformity of the automa-

tion. On account of this, all operations regarding connection to the 

mains electricity, as well as product testing, commissioning and 

maintenance, must be performed exclusively by a qualified and 

skilled technician!
• 

Before proceeding with the product’s installation, check that all materi-

als are in good working order and are suitable for the intended applica-

tions

• 

The product is not intended for use by persons (including children) with 

reduced physical, sensory or mental capacities, nor by anyone lacking 

sufficient experience or familiarity with the product

• 

Children must not play with the appliance

• 

Do not allow children to play with the control devices of the product. 

Keep the remote controls out of reach of children 

CAUTION 

- In order to avoid any danger from inadvertent resetting of the 

thermal cut-off device, this appliance must not be powered through an 

external switching device, such as a timer, or connected to a supply that 

is regularly powered or switched off by the circuit

• 

Provide a disconnection device (not supplied) in the plant’s mains pow-

er supply, with a contact opening distance that ensures complete dis-

connection under the conditions envisaged by Overvoltage Category III

• 

Handle the product with care during installation, taking care to avoid 

crushing, knocks, falls or contact with liquids of any kind. Keep the 

product away from sources of heat and open flames. Failure to ob-

serve the above can damage the product and increase the risk of dan-

ger or malfunctions. If this should happen, stop installation immediately 

and contact the Customer Service

• 

The manufacturer assumes no liability for damage to property, items or 

persons resulting from non-compliance with the assembly instructions. 

In such cases the warranty does not cover material defects 

• 

The weighted sound pressure level of the emission A is lower than 70 

dB(A) 

• 

Cleaning and maintenance to be carried out by the user must not be 

effected by unsupervised children

KNOWLEDGE OF THE PRODUCT AND PREPARATION FOR INSTALLATION

other than the intended use described and use in environmental 

conditions other than those described in this manual should be 

considered improper and forbidden!

The main part of the automation consists of a control unit and two elec-

tromechanical gearmotors. Each gearmotor is provided with a 24 V direct 

current motor and a reduction unit with worm screws; it is equipped with 

a mechanical release and key which allows you to manually move the 

gate in the event of a lack of power supply.

The command control unit manages the operation of all of the automation, 

and is made up of an electronic board and an integrated radio receiver, to 

receive commands sent by the user via the transmitter. It can memorise 

up to 256 ECCO5... transmitters (if these are memorised in “Mode 1”) and 

up to 6 PH200 photocell pairs.

Connection of the control unit to the various devices takes place via a sin-

gle cable with two electrical conductors (“ECSbus” system). Furthermore, 

the control unit can be powered by a fixed electrical network (230 V) or, 

alternatively, by della linea Nice Home SOLEKIT solar power system.

If powered from the grid, it can host a buffer battery (mod. PR100, option-

al accessory) which ensures that the automation can execute certain 

NOTE TO MANUAL

• This manual describes how to implement a complete and opti-

mal automation, like that shown in fig. 3, using all della linea Nice 

Home devices which form part of the automation system known 

as “RIVA200”. Some of these devices are optional and may not 

be present in this kit. For a complete overview of the devices, 

see della linea Nice Home product catalogue.

• This manual is designed as a step-by-step guide. Therefore, for 

the safety and ease of assembly and programming work, we 

advice you to carry out all the operations described in the same 

order in which they are presented.

–––  STEP 2  –––

2.1 -  PRODUCT DESCRIPTION AND INTENDED USE

The devices in this kit, plus other accessories (some optional and some 

not included), together form the automation system called “RIVA200”, 

designed for automation of a hinged gate for “residential” use. 

All uses 

GENERAL SAFETY WARNINGS AND PRECAUTIONS (Instructions translated from Italian)

Summary of Contents for RIVA Series

Page 1: ...pour l installation et l utilisation EN Instructions and warnings for installation and use IT Istruzioni ed avvertenze per l installazione e l uso PL Instrukcje i ostrze enia do instalacji i u ytkowan...

Page 2: ......

Page 3: ...R ET CONNECTER LE FEU CLIGNOTANT FL200 13 6 4 CONNEXION LECTRIQUE LA LOGIQUE DE COMMANDE CLB201 13 PROGRAMMATION PHASE 7 17 7 1 RACCORDEMENT DE L ALIMENTATION LECTRIQUE 17 7 2 V RIFICATIONS INITIALES...

Page 4: ...ne peut tre utilis par des personnes y compris des en fants dont les capacit s physiques sensorielles ou mentales sont limit es ou ne disposant pas de l exp rience ou des connaissances n cessaires Les...

Page 5: ...rifier que chaque dispositif installer se trouve dans une position pro t g e l abri des chocs accidentels V rifier les limites d encombrement en consultant la fig 2 Pr voir des but es de fin de course...

Page 6: ...ont positionn s selon un sch ma standard et commun Les dispositifs utilis s sont a 1 logique de commande CLB201 b 1 clignotant avec antenne incorpor e FL200 c 1 paire de photocellules PH200 compos e d...

Page 7: ...Fran ais Fran ais 7 D E E D A B C d d c c b a 4 3 1 254 mm 72 5 mm 320 mm 81 mm 52 mm 2 PH200 FL200 CLB201 ECCO5WO ECCO5BO RIVA200...

Page 8: ...n le levier d accro chage d j fix au vantail fig 10 TR S IMPORTANT s assurer que le vantail est bien fix aux gonds de la colonne mur de mani re ce qu il NE PUISSE PAS TRE SOULEV fig 11 Ceci permet de...

Page 9: ...Fran ais 9 Fran ais 5 6 1 2 7 8...

Page 10: ...10 Fran ais Fran ais 9 10 OK OK 11...

Page 11: ...Fran ais 11 Fran ais 12 13 90 90 180...

Page 12: ...12 Fran ais Fran ais 14 15 16...

Page 13: ...Fran ais 13 Fran ais Clack 1 2 3 17 18...

Page 14: ...14 Fran ais Fran ais 4 5 1 2 3 19 A B C...

Page 15: ...fig 26 05 Brancher le c ble lectrique sur les bornes de l metteur et du r cepteur en parall le entre eux et raccord s la fin la borne pr sente sur la logique de commande fig 8 Il n est pas n cessaire...

Page 16: ...Fran ais 16 Fran ais TX RX M M M M FLASH BUS STOP SbS NC NO 23 FL200 PH200 M2 M1 B A 21 22 bleu jaune vert marron bleu jaune vert marron A 24 25...

Page 17: ...Fran ais Fran ais 17 3 1 26 4 2 5 1 Led SAFE 3 2 4 5 mm...

Page 18: ...Fran ais 18 Fran ais 27 6 mm x4 5 B 6 mm x4 5 A 2 1 aerial flash 2 1 1 6 2 7 3 8 4 9...

Page 19: ...de la reconnaissance la LED STOP A fig 29 doit rester allum e tandis que la LED P2 B fig 29 doit s teindre Si la LED P2 clignote cela signifie qu il y a une erreur voir le paragraphe 10 5 R solution...

Page 20: ...Fran ais 20 Fran ais 29 A C B M M M M FLASH BUS STOP SbS 28 A TX RX 32 A B 30 A B 31 LED T5 T2 T4 T3 T1 B...

Page 21: ...lules bords sensibles etc En par ticulier chaque fois qu un dispositif intervient la LED ECsBus sur la logique de commande effectue un clignotement plus long qui confirme qu elle reconna t l v nement...

Page 22: ...l Appuyer 2 fois sur la touche T2 3 Ouverture 2 vantaux partiels 1 4 de la course Appuyer 3 fois sur la touche T2 4 Ouverture 2 vantaux partiels mi course Appuyer 4 fois sur la touche T2 Force moteurs...

Page 23: ...par le syst me d alimentation nergie solaire SOLEKIT il NE DOIT PAS L TRE AUSSI simultan ment par le secteur lectrique Pour connecter le syst me d alimentation nergie solaire SOLEKIT la logique de com...

Page 24: ...Ea 14 et degr s 45 N 02 Dans les graphiques Nord ou Sud pr sents dans les instructions du guide du kit SOLEKIT identifier la courbe correspondant aux degr s de latitude du lieu ex 45 N 03 Choisir la...

Page 25: ...sitif type 1er dispositif type NO NC 8 2K NO En parall le note 2 note 1 En parall le NC note 1 In s rie note 3 In s rie 8 2K En parall le In s rie note 4 Note 1 Il est possible de combiner NO et NF en...

Page 26: ...allation d autres photocel lules en plus de celles d j fournies de s rie avec RIVA200 Dans un auto matisme pour portails 2 vantaux il est possible de les placer comme le montre la fig 39 Pour la recon...

Page 27: ...ne phase d effacement pour chaque touche m moris e 01 Appuyer sur la touche P1 B fig 41 de la logique de commande et la maintenir enfonc e 02 Attendre que la LED P1 A fig 41 s allume dans les trois se...

Page 28: ...effacement se terminera automatiquement Pour plus d informations sur le s lecteur DS100 consulter le manuel d instructions du produit ou visiter le site www niceforyou com 9 5 R SOLUTION DES PROBL ME...

Page 29: ...nnaissance sur la logique de commande V rifier que toutes les paires de photocellules sur ECSbus ont des adresses diff rentes voir Tableau 8 1 clignotement tr s lent Le RX re oit un excellent signal F...

Page 30: ...du clignotant Voir le Tableau 12 Clignotement rapide Court circuit sur ECSbus Une surcharge a t relev e et donc l alimentation sur l ECSbus a t teinte V rifier en d connectant ventuellement les dispos...

Page 31: ...command e par un microcontr leur 8 Bit en technologie flash Un transformateur l int rieur de la logique de commande mais s par de la carte r duit la tension de secteur la tension nominale de 24 Vcc ut...

Page 32: ...e CLB201 est conforme la DIRECTIVE 1999 5 CE DU PARLEMENT EUROP EN ET DU CONSEIL du 9 mars 1999 concernant les quipements hertziens et les terminaux de communication et la reconnaissance mutuelle de l...

Page 33: ...e portail L op ration manuelle doit tre utilis e en cas de panne de courant ou d anomalies de l installation Dans le cas d une panne de courant il est gale ment possible d utiliser une batterie tampon...

Page 34: ...N de s rie Ann e de fabrication Lieu d installation adresse Satisfait les exigences essentielles des directives suivantes 2006 42 CE Directive Machines et ce qui est pr vu par les normes harmonis es s...

Page 35: ...ELLS 13 6 3 INSTALL AND CONNECT FL200 FLASHING INDICATOR 13 6 4 ELECTRICAL CONNECTION TO CLB201 CONTROL UNIT 13 PROGRAMMING STEP 7 17 7 1 POWER SUPPLY CONNECTION 17 7 2 PRELIMINARY CHECKS 17 7 3 CONNE...

Page 36: ...the appliance Do not allow children to play with the control devices of the product Keep the remote controls out of reach of children CAUTION In order to avoid any danger from inadvertent resetting of...

Page 37: ...s by referring to fig 2 Provide end stops at ground level either for opening or for closing of the gate Check that the fixing area of the gearmotor is compatible with its dimen sions fig 2 3 2 PRODUCT...

Page 38: ...l devices must be positioned in view of the automation away from its moving parts at a minimum height of 1 5 m from the floor ground not accessible to strangers 4 1 2 Establish the position of all the...

Page 39: ...English 5 English D E E D A B C d d c c b a 4 3 1 254 mm 72 5 mm 320 mm 81 mm 52 mm 2 PH200 FL200 CLB201 ECCO5WO ECCO5BO RIVA200...

Page 40: ...the foundation case bush the attachment lever already fixed to the leaf fig 10 VERY IMPORTANT check that the leaf is firmly attached to the column wall hinges in such a way that IT CAN NOT BE LIFTED...

Page 41: ...English 7 English 5 6 1 2 7 8...

Page 42: ...8 English English 9 10 OK OK 11...

Page 43: ...English 9 English 12 13 90 90 180...

Page 44: ...10 English English 14 15 16...

Page 45: ...English 11 English Clack 1 2 3 17 18...

Page 46: ...12 English 4 5 1 2 3 19 English A B C...

Page 47: ...ls of the TX and RX which must be connected in parallel to each other then connected to the terminal on the control unit Fig 8 It is not necessary to observe any polarity Put back in place in the foll...

Page 48: ...14 English English TX RX M M M M FLASH BUS STOP SbS NC NO 23 FL200 PH200 M2 M1 B A 21 22 blue yellow green brown blue yellow green brown A 24 25...

Page 49: ...English 15 English 3 1 26 4 2 5 1 Led SAFE 3 2 4 5 mm...

Page 50: ...16 English English 27 6 mm x4 5 B 6 mm x4 5 A 2 1 aerial flash 2 1 1 6 2 7 3 8 4 9 OG LNE ZALECENIA I OSTRZE ENIA DOTYCZ CE BEZPIECZE STWA Instrukcja przet umaczona z j zyka w oskiego...

Page 51: ...completion the STOP LED A fig 29 must remain lit whilst the P2 LED B fig 29 must go out If the P2 LED flashes it means that an error has occurred see section 10 5 Troubleshooting The phase of self lea...

Page 52: ...18 English English 29 A C B M M M M FLASH BUS STOP SbS 28 A TX RX 32 A B 30 A B 31 LED T5 T2 T4 T3 T1 B...

Page 53: ...l the safety devices one by one photocells safety edges etc In particular each time a device is activated the ECSbus LED on the control unit flashes longer con firming that the control unit has recogn...

Page 54: ...1 and motor 2 discharge in opening 1 No discharge Press T4 once 2 0 1s Minimum Press T4 twice 3 0 2s Press T4 three times 4 0 3s Press T4 four times 5 0 4s Medium Press T4 five times 6 0 5s Press T4...

Page 55: ...ED by the electricity grid at the same time To connect the SOLEKIT solar power supply system to the control unit see fig 37 and refer to the SOLEKIT instruction manual When automation is powered by th...

Page 56: ...the value of Ea and the degrees of latitude of the location Ex Ea 14 and degrees 45 N 02 In the graphs North or South shown in the SOLEKIT kit instruction manual locate the curve which relates to the...

Page 57: ...NO and NC combinations are possible by placing the 2 contacts in parallel taking care to place a 8 2 k resistance in parallel to the NC contact thus enabling the combination of 3 devices Normally Ope...

Page 58: ...ed 10s you must read the instructions in the following paragraphs before you proceed with their execution For correct photocells recognition by the control unit you need to carry out its addressing th...

Page 59: ...ode 1 one deletion phase is sufficient and at point 3 you may press any key If the transmitter is stored in mode 2 a deletion phase is required for each memorised key 01 Press the P1 key B key fig 41...

Page 60: ...he deletion will stop automatically For more information on the DS100 selector switch refer to the product instruction manual or visit www niceforyou com 9 5 TROUBLESHOOTING Table 10 contains instruct...

Page 61: ...control unit Repeat the recognition procedure on the control unit Check that all photocell pairs on the ECSbus have different addresses see Table 8 1 very slow flash The RX is receiving optimum signa...

Page 62: ...l as on the flasher see Table 12 Fast flashing ECSbus short circuit An overload has been detected and therefore the power supply to the ECSbus has been turned off Check possibly by disconnecting each...

Page 63: ...ing command STOP inputv For normally closed or normally open contacts and or for constant resistance of 8 2 K or normally closed contacts with self recognition of the normal state any variation from t...

Page 64: ...cordance with the following harmonised standards Health and safety Art 3 1 a EN 62479 2010 Electrical safety Art 3 1 a EN 60950 1 2006 A11 2009 A12 2011 A1 2010 A2 2013 Electromagnetic compatibility A...

Page 65: ...ormed in the case of a power outage or in the event of anomalies affecting the system In case of a power outage a back up battery can be used model PR100 not supplied see Chapter 10 2 In the event of...

Page 66: ...tomation hinged leaves motorised gate Serial N Year of manufacture Location address Complies with the essential requirements of the following directives 2006 42 EC Machines Directive and as provided f...

Page 67: ...3 INSTALLARE E COLLEGARE IL SEGNALATORE LAMPEGGIANTE FL200 13 6 4 COLLEGAMENTO ELETTRICO ALLA CENTRALE CLB201 13 PROGRAMMAZIONE PASSO 7 17 7 1 ALLACCIAMENTO DELL ALIMENTAZIONE 17 7 2 VERIFICHE INIZIAL...

Page 68: ...con mancanza di esperienza o di conoscenza I bambini non devono giocare con l apparecchio Non permettere ai bambini di giocare con i dispositivi di comando del prodotto Tenere i telecomandi lontano d...

Page 69: ...coppia Tx e Rx Accertarsi che ciascun dispositivo da installare sia collocato in una posi zione protetta e al riparo da urti accidentali Verificare i limiti di ingombro facendo riferimento alla fig 2...

Page 70: ...ore lampeggiante con antenna incorporata FL200 c 1 coppia di fotocellule PH200 composta da un TX ed un RX d 2 motoriduttori elettromeccanici RIVA200 AVVERTENZA Alcuni di questi dispositivi sono opzion...

Page 71: ...Italiano D E E D A B C d d c c b a Italiano 5 4 3 1 254 mm 72 5 mm 320 mm 81 mm 52 mm 2 PH200 FL200 CLB201 ECCO5WO ECCO5BO RIVA200...

Page 72: ...della cassa di fondazione la leva di aggancio gi fissata all anta fig 10 MOLTO IMPORTANTE controllare che l anta sia ben fissata ai cardini della colonna muro in modo che NON POSSA ESSERE SOLLEVATA f...

Page 73: ...Italiano 7 Italiano 5 6 1 2 8 7...

Page 74: ...8 Italiano Italiano 9 10 OK OK 11...

Page 75: ...Italiano 9 Italiano 12 13 90 90 180...

Page 76: ...10 Italiano Italiano 14 15 16...

Page 77: ...Italiano 11 Italiano Clack 1 2 3 17 18...

Page 78: ...12 Italiano Italiano 4 5 1 2 3 19 A B C...

Page 79: ...l TX e del RX che vanno collegati tra loro in parallelo e alla fine collegati al morsetto presente sulla centrale fig 8 Non necessario rispettare alcuna polarit Riposizionare in ordine il guscio inter...

Page 80: ...Italiano 14 Italiano 24 25 TX RX M M M M FLASH BUS STOP SbS NC NO 23 FL200 PH200 M2 M1 blu giallo verde marrone blu giallo verde marrone A B A 21 22...

Page 81: ...Italiano Italiano 15 3 1 26 4 2 5 1 Led SAFE 3 2 4 5 mm...

Page 82: ...Italiano 16 Italiano 27 6 mm x4 5 B 6 mm x4 5 A 2 1 aerial flash 2 1 1 6 2 7 3 8 4 9...

Page 83: ...dimento dei dispositivi 03 Al termine dell apprendimento il LED STOP A fig 29 deve rimane re acceso mentre il LED P2 B fig 29 si deve spegnere Se il LED P2 lampeggia significa che c qualche errore ved...

Page 84: ...Italiano 18 Italiano 29 A C B M M M M FLASH BUS STOP SbS 28 A TX RX 32 A B 30 A B 31 LED T5 T2 T4 T3 T1 B...

Page 85: ...ositivi di sicurezza presenti nell impianto fotocellule bordi sensibili ecc In particolare ogni volta che un dispositivo interviene il LED ECSbus sulla centrale esegue un lampeggio pi lungo a conferma...

Page 86: ...Premere 1 volta il tasto T4 2 0 1s Minimo Premere 2 volte il tasto T4 3 0 2s Premere 3 volte il tasto T4 4 0 3s Premere 4 volte il tasto T4 5 0 4s Medio Premere 5 volte il tasto T4 6 0 5s Premere 6 v...

Page 87: ...LEKIT alla centrale vedere fig 37 e fare riferimento al manuale istruzioni di SOLE KIT Quando l automazione alimentata da pannello solare trascorsi 60 s dal termine di una manovra la centrale automati...

Page 88: ...pa terrestre presente nelle istruzioni manuale del kit SOLE KIT trovare il punto di installazione dell impianto guindi rilevare il valore di Ea ed i gradi di latitudine del luogo Es Ea 14 e gradi 45 N...

Page 89: ...o bordi sensibili Con opportuni accorgimenti possibile collegare all ingresso STOP pi di un dispositivo anche di tipo diverso vedere Tabella 7 TABELLA 7 2 dispositivo tipo 1 dispositivo tipo NA NC 8 2...

Page 90: ...nali In qualsiasi momento possibile installare ulteriori fotocellule oltre a quelle gi fornite di serie con RIVA200 In un automatismo per cancelli a 2 ante possibile porle secondo quanto rappresentato...

Page 91: ...ere premuto un tasto qualsiasi Se il trasmettitore memorizzato in Modo 2 occorre una fase di cancellazione per ogni tasto memorizzato 01 Premere e tenere premuto il tasto P1 B fig 41 sulla centrale 02...

Page 92: ...ni sul selettore DS100 consultare il manuale istru zioni del prodotto o visitare il sito www niceforyou com 9 5 RISOLUZIONE DEI PROBLEMI Nella Tabella 10 possibile trovare utili indicazioni per affron...

Page 93: ...rendimento 9 3 3 Apprendimento altri dispositivi possibile che vi siano dispositivi guasti verificare e sostituire 2 lampeggi pausa di 1 secondo 2 lampeggi Intervento di una fotocellula All inizio del...

Page 94: ...ilevato un sovraccarico e quindi stata spenta l alimentazione sull ECSbus Verificare eventualmente scol legando uno alla volta i dispositivi Per accendere l alimentazione all ECSbus sufficiente dare u...

Page 95: ...le Ingresso STOP Per contatti normalmente aperti e o per resistenza costante 8 2k oppure contatti nor malmente chiusi con autoapprendimento dello stato normale una variazione rispetto allo stato memor...

Page 96: ...le apparecchiature radio e le apparecchiature terminali di comunicazione e il reciproco riconoscimento della loro conformit secondo le seguenti norme armonizzate Protezione della salute art 3 1 a EN 6...

Page 97: ...razione manuale deve essere eseguita nel caso di mancanza di corrente o di anomalie dell impianto Nel caso di mancanza di corrente anche possibile utilizzare una batteria tampone mod PR100 non in dota...

Page 98: ...azione cancello ad ante battenti motorizzato Matricola N Anno di fabbricazione Ubicazione indirizzo Soddisfa i requisiti essenziali delle seguenti direttive 2006 42 CE Direttiva Macchine e quanto prev...

Page 99: ...ZY LAMP SYGNALIZUJ C FL200 13 6 4 POD CZENIE ELEKTRYCZNE CENTRALI CLB201 13 PROGRAMOWANIE KROK 7 17 7 1 POD CZENIE ZASILANIA 17 7 2 KONTROLE POCZ TKOWE 17 7 3 ROZPOZNAWANIE PRZY CZONYCH URZ DZE 17 7 4...

Page 100: ...do u ycia Produkt nie jest przeznaczony do obs ugi przez osoby w tym dzieci o ograniczonych zdolno ciach fizycznych zmys owych b d umys o wych lub przez osoby nieposiadaj ce odpowiedniego do wiadczen...

Page 101: ...e zapewni w a ciwe wyr w nanie pary Tx i Rx Upewni si e ka de urz dzenie kt re ma by zainstalowane znaj duje si w bezpiecznym miejscu i jest chronione przed przypadkowymi uderzeniami Sprawdzi ogranic...

Page 102: ...ane urz dzenia to a 1 centrala steruj ca CLB201 b 1 lampa sygnalizuj ca z wbudowan anten FL200 c 1 para fotokom rek PH200 z o ona z TX i RX d 2 motoreduktory elektromagnetyczne RIVA200 OSTRZE ENIE Nie...

Page 103: ...Polski 5 Polski D E E D A B C d d c c b a 4 3 1 254 mm 72 5 mm 320 mm 81 mm 52 mm 2 PH200 FL200 CLB201 ECCO5WO ECCO5BO RIVA200...

Page 104: ...ymocowane do kolumny cia ny w spos b UNIEMO LIWIAJ CY JEGO PODNIESIENIE rys 11 Ma to na celu zapewnienie odpowiedniego kontaktu z ko ami z baty mi wa u silnika 11 Je eli brama posiada w asne blokady m...

Page 105: ...Polski 7 Polski 5 6 1 2 7 8...

Page 106: ...8 Polski Polski 9 10 OK OK 11...

Page 107: ...Polski 9 Polski 12 13 90 90 180...

Page 108: ...10 Polski Polski 14 15 16...

Page 109: ...Polski 11 Polski Clack 1 2 3 17 18...

Page 110: ...12 Polski Polski 4 5 1 2 3 19 A B C...

Page 111: ...y po czy mi dzy sob r wnolegle i na koniec po czy je do zacisku obecnego na centrali rys 8 Nie jest konieczne przestrzeganie ad nej biegunowo ci U o y w odpowiednim porz dku obudow wewn trzn nast p ni...

Page 112: ...14 Polski Polski TX RX M M M M FLASH BUS STOP SbS NC NO 23 FL200 PH200 M2 M1 B A 21 22 niebieski ty zielony br zowy niebieski ty zielony br zowy A 24 25...

Page 113: ...Polski 15 Polski 3 1 26 4 2 5 1 Led SAFE 3 2 4 5 mm...

Page 114: ...16 Polski Polski 27 6 mm x4 5 B 6 mm x4 5 A 2 1 aerial flash 2 1 1 6 2 7 3 8 4 9...

Page 115: ...P2 miga oznacza to obecno b du patrz punkt 10 5 Rozwi zywanie problem w Faza rozpoznawania pod czonych urz dze mo e by powt rzona w jakimkolwiek momencie r wnie po zako czeniu monta u na przyk ad je...

Page 116: ...18 Polski Polski 29 A C B M M M M FLASH BUS STOP SbS 28 A TX RX 32 A B 30 A B 31 LED T5 T2 T4 T3 T1 B...

Page 117: ...t re urz dzenie dioda LED BlueBUS znajduj ca si na centrali wykona d u sze migni cie jako potwierdzenie e centrala rozpozna a zdarzenie 04 W celu kontroli stanu fotokom rek i w szczeg lno ci w celu sp...

Page 118: ...0 1s Minimalny Nacisn 2 razy przycisk T4 3 0 2s Nacisn 3 razy przycisk T4 4 0 3s Nacisn 4 razy przycisk T4 5 0 4s redni Nacisn 5 razy przycisk T4 6 0 5s Nacisn 6 razy przycisk T4 7 0 6s Nacisn 7 razy...

Page 119: ...R WNOCZE NIE ZASILANA r wnie z sieci elektrycznej W celu pod czenia systemu zasilania centrali energi s oneczn SOLE KIT nale y si zapozna z rys 37 i odnie si do instrukcji SOLEKIT Gdy automatyka jest...

Page 120: ...nale punkt monta u urz dzenia nast pnie nale y odczyta war to Ea i szeroko geograficzn miejsca Np Ea 14 i stopni 45 N 02 Na wykresach P noc lub Po udnie znajduj cych si w instrukcji zestawu SOLEKIT od...

Page 121: ...wi cej ni jednego urz dzenia nawet r nych rodzaj w patrz Tabela 7 TABELA 7 2 urz dzenie typu 1 urz dzenie typu NO NC 8 2K NO R wnolegle uwaga 2 uwaga 1 R wnolegle NC uwaga 1 Szeregowo uwaga 3 Szerego...

Page 122: ...pcjonalnych fotokom rek W dowolnym momencie mo liwe jest zainstalowanie dodatkowych foto kom rek opr cz fotokom rek dostarczonych w serii z RIVA200 W auto matyce do bram przesuwnych 2 skrzyd owych mo...

Page 123: ...bie 2 ka dy wczytany przycisk nale y skasowa oddzielnie 01 Nacisn i przytrzyma wci ni ty przycisk P1 B rys 41 na centrali 02 Odczeka na za wiecenie si diody LED P1 A rys 41 wi c trzy sekundy 03 Nacisk...

Page 124: ...3 W przeciwnym razie faza kasowania zako czy si automatycznie W celu uzyskania dodatkowych informacji na temat prze cznika DS100 nale y si zapozna z instrukcj produktu lub odwiedzi stron www nicefory...

Page 125: ...dopodobnie fotokom rka jest uszkodzona 3 szybkie migni cia i 1 sekunda przerwy Urz dzenie nie zosta o rozpozna ne przez central Powt rzy procedur wczytywania centrali Sprawdzi czy wszystkie pary foto...

Page 126: ...diody Zwarcie na ECSbus Zosta o odczytane przeci enie wi c zasilanie ECSbus zosta o wy czone Sprawdzi ewentualnie od czaj c urz dzenia jedno za drugim W celu w czenia zasilania ECSbus wystarczy wyda p...

Page 127: ...rzez mikrosterownik 8 Bit w technologii flash Wbudowany do centrali ale oddzielony od karty transformator redukuje napi cie sieciowe do napi cia nominalnego 24 V stosowanego w ca ej automatyce Maksyma...

Page 128: ...radiowych i ko cowych urz dze telekomunikacyjnych oraz wzajemnego uznawania ich zgodno ci zgodnie z nast puj cymi normami zharmonizowanymi Ochrona zdrowia art 3 1 a EN 62479 2010 Bezpiecze stwo elekt...

Page 129: ...amy Otwarcie r czne nale y wykona w przypadku braku pr du lub usterki instalacji W razie braku pr du mo na r wnie u ywa akumulatora awaryjnego mod PR100 nieznajduj ce si na wyposa eniu patrz rozdz 10...

Page 130: ...ie automatyka nap dzana brama skrzyd owa Nr seryjny Rok produkcji Lokalizacja adres Spe nia podstawowe wymogi nast puj cych dyrektyw 2006 42 WE Dyrektywa Maszynowa Jest r wnie zgodna z nast puj cymi n...

Page 131: ......

Page 132: ...com Service Apr s Vente France En cas de panne merci de contacter obligatoirement notre Service Apr s Vente par t l phone ou par email 0 820 859 203 Service 0 15 min prix appel niceservice niceforyou...

Reviews: