IMPORTANT
Newmar recommends the "Capacity - Generator"
['Genset Capacity'] function be set to '50 Amps' in
coaches equipped with a 12,500 watt generator.
IMPORTANT
Newmar recommends the "Load Shedding" function
be set to 'enabled.'
PHASE DETECTION
Set the Phase Detection setting to "manual" if you want to manually control the phase selection. Set the Phase
Detection setting to "automatic" [default setting] to allow the RV-C transfer switch to auto-detect the supplied phase
based on the available power source, such as dual phase (240 volts), 50 Amp AC power.
DEFAULT PHASE
Selects the default phase setting for the load shedding function: single or dual phase.
CAPACITY-SINGLE PHASE
This sets the load shedding amperage value for the single phase selection.
IMPORTANT
Newmar recommends the "Capacity - Single Phase" function be set to '30 Amps' or less (less if plugged into
less than 30 amp). Failure to do so may result in tripping of the breaker supplying power to the coach.
CAPACITY-DUAL PHASE
This sets the load shedding amperage value for the dual phase selection.
CAPACITY-GENERATOR
This setting specifies the maximum available amperage the
generator can output.
LOAD SHEDDING
Enabling the load shedding function allows the control
system to automatically manage the AC power system
based on the capacity settings from Screen 1. The system
will shed (turn OFF) configured AC power devices in order
to maintain a maximum phase capacity AC amperage
usage.
GENERATOR SETTLING
This setting allows the generator to "settle down" and level out before a load is allowed to be put on the system.