![Neptune 13458-000 Installation And Maintenance Manual Download Page 74](http://html1.mh-extra.com/html/neptune/13458-000/13458-000_installation-and-maintenance-manual_1668232074.webp)
Installing the UPS
To install the UPS, complete the following steps.
Figure 71 – UPS Mounted on a Wall
1. To mount the UPS to a wall near the Gateway, use
corrosion-resistant hardware through the four holes
provided in the mounting bracket. See Figure 71.
The Gateway and UPS can be mounted directly to a wall or
strut channel that is attached to a wall.
The mounting brackets for the Gateway and UPS have the
same horizontal and vertical hole spacing. This allows you to
mount both of them on the same two pieces of the strut
channel. The two pieces of the strut channel can be mounted
horizontally (Gateway and UPS in a "side by side"
arrangement) or the strut channel can be mounted vertically
(Gateway and UPS in a "stacked" arrangement).
Be sure to mount the UPS in close proximity (within 3 feet) of
the Gateway
.
Figure 72 – UPS with VAC Input
Wired
2. Remove the two screws from the cover on the UPS, and
remove the cover.
3. Wire the 120 VAC input through the lower knockout
hole. See Figure 72.
56
R900 Gateway Installation and Maintenance Guide
Chapter 4: Installation of the Gateway
Summary of Contents for 13458-000
Page 2: ......
Page 3: ...R900 Gateway v4 Installation and Maintenance Guide...
Page 6: ...This page intentionally left blank...
Page 149: ......