Ethernet Termination
This section provides information on the termination of the
Ethernet cable.
Straight-Through Ethernet Cable
For most installations of the Gateway, the straight-through
Ethernet cable is used. Use a shielded category 5e or better
Ethernet cable that is rated for outdoor use and is sunlight
resistant, for example, Belden cable Part No. 7919A. Terminate
the Ethernet cable according to Figure 107 using the T-568B
wiring standard for both ends. One end should already be
terminated to the switch or hub.
Figure 107 – Straight-Through Ethernet Cable
Crossover Ethernet Cable
In some cases, a crossover Ethernet cable is required. For example:
l
You require a cable to connect two Ethernet devices together
without a hub.
l
You connect two hubs together.
114
R900 Gateway Installation and Maintenance Guide
Appendix D Cellular and Ethernet Considerations