
NX50 Troubleshooting Manual
Responding to alarms
Page 1-12
Issue 6.0 2019-04-01
Controller: External PDM
Inhibit
This alarm occurs if the external PDM inhibit circuit, wired to the
control/interface PWB, is closed. When this alarm occurs, the
transmitter immediately inhibits the PDM and the transmitter's
output power drops to 0 W. The transmitter will automatically
recover when the condition is cleared. Ensure the transmitter is
set to RF Off and disconnect the PDM inhibit circuit from the
transmitter (see
“Controller: External PDM Inhibit” on page 1-43
).
Measure the impedance of the interlock circuit. If the impedance
measures short circuit (low impedance) the PDM inhibit is closed,
and it will be necessary to locate the external device that is
causing this condition. If the impedance does not measure short
circuit, verify the PDM inhibit circuitry has been properly
configured. If the PDM inhibit circuitry is properly configured and
the alarm persists, replace the control/interface PWB (see
“Control/interface PWB replacement” on page 1-64
Controller: External
Reset
This alarm is only visible in the transmitter logs, and indicates the
controller was reset by triggering the controller's reset pin. If this
alarm continues to occur unexpectedly, replace the control/
interface PWB
“Control/interface PWB replacement” on
Controller: Fast SWR
Shutback
This alarm indicates the peak reflected power measured by the
directional coupler at the output of the transmitter has exceeded
the factory-set threshold. When this alarm occurs, the transmitter
immediately inhibits the PDM and RF drive
(see
of the Operations & Maintenance Manual). Once the
fault clears, the transmitter will automatically recover, either to the
power setpoint, or to a reduced power as determined by the
cutback routine
(see
of the Operations &
Maintenance Manual). If this alarm occurs in conjunction with the
Exciter's SWR Shutback alarm, it generally indicates a fault in the
transmitter's external RF output network (e.g., rigid-line, antenna,
etc.). If this alarm is occurring while the Exciter's SWR Shutback
alarm is not, verify the wiring between the directional coupler and
the control/interface PWB is not damaged. If not, verify the Fast
SWR Shutback threshold is set properly (contact Nautel to obtain
the correct setting for your transmitter). If this threshold is set
correctly and the alarm persists, replace the control/interface
PWB (see
“Control/interface PWB replacement” on page 1-64
).
Alarm (with Prefix)
Description and Troubleshooting Action
Summary of Contents for NX50
Page 2: ......
Page 4: ......
Page 8: ...NX50 Troubleshooting Manual Page viii Issue 6 0 2019 04 01...
Page 10: ...NX50 Troubleshooting Manual Page x Issue 6 0 2019 04 01...
Page 108: ...NX50 Troubleshooting Manual Responding to alarms Page 1 98 Issue 6 0 2019 04 01...
Page 153: ...NX50 Troubleshooting Manual Reading Electrical Schematics Page 4 6 Issue 6 0 2019 04 01...
Page 184: ...Issue 6 0 2019 04 01 MD 4 Figure MD 4 NAPI95A 01 Power Module Interface PWB...
Page 188: ...Issue 6 0 2019 04 01 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 192: ...Issue 6 0 2019 04 01 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 198: ...Issue 6 0 2019 04 01 MD 18 Figure MD 18 Fan Tray Assembly 207 8133 B1 B2 J1 AIR FLOW AIR FLOW...
Page 201: ...Issue 6 0 2019 04 01 MD 21 Figure MD 21 NAFP106B 01 Directional Coupler A1 DETAIL...
Page 204: ......