![Nautel NX50 Troubleshooting Manual Download Page 18](http://html1.mh-extra.com/html/nautel/nx50/nx50_troubleshooting-manual_3580193018.webp)
NX50 Troubleshooting Manual
Responding to alarms
Page 1-8
Issue 6.0 2019-04-01
Table 1.1: Troubleshooting Alarms
Alarm (with Prefix)
Description and Troubleshooting Action
Controller: Audio Loss
Shutdown
This alarm occurs if the modulation level is below the preset
threshold for the designated period of time set in the Audio Loss
settings of the current preset, and the desired action was set to
RF Inhibit. This will cause the transmitter to shut down its RF
output until the exciter determines that the modulation source has
returned. If this alarm is unexpected, check the audio inputs
specified in the preset and verify there is signal present.
Controller: Arc Shutback
This alarm indicates the transmitter has entered a shutback (see
Shutback on page 3.1.10 of the Operations & Maintenance
Manual for a description of the shutback routine) due to one of the
rack controller’s arc detectors being activated. When this fault
occurs, the transmitter immediately inhibits PDM and the
transmitter's output power drops to 0 W. Once the fault clears the
transmitter will automatically recover, either to the power setpoint,
or to a reduced power as determined by the cutback routine (see
of the Operations & Maintenance Manual
for a description of the cutback routine). Visually inspect the inside
of the transmitter to locate the fault causing the arc detector to
trigger.
Controller: Brownout
Reset
This alarm is only visible in the transmitter logs, and indicates the
controller was reset because its +5 V power supply voltage was
less than +4.3 V, but remained above +1.4 V, and then
subsequently recovered. This alarm should occur concurrently
with other alarms. Follow the troubleshooting information for the
associated alarms. If the alarm persists without the presence of
other alarms, replace the control/interface PWB
interface PWB replacement” on page 1-64
).
Controller: Combiner
Interlock Open
This alarm will only occur if the transmitter is connected in a
combined system. The alarm indicates that the interlock signal
from the combiner is open. When this alarm occurs, the
transmitter immediately inhibits the PDM and the transmitter's
output power drops to 0 W. The transmitter will automatically
recover when the condition is cleared. Check the combiner for a
condition that may cause it to open the interlock to the transmitter.
If so, troubleshoot the cause of that condition. If not, inspect the
wiring between the combiner and the transmitter and verify there
is no damage. If the alarm persists, replace the control/interface
PWB
“Control/interface PWB replacement” on page 1-64
).
Summary of Contents for NX50
Page 2: ......
Page 4: ......
Page 8: ...NX50 Troubleshooting Manual Page viii Issue 6 0 2019 04 01...
Page 10: ...NX50 Troubleshooting Manual Page x Issue 6 0 2019 04 01...
Page 108: ...NX50 Troubleshooting Manual Responding to alarms Page 1 98 Issue 6 0 2019 04 01...
Page 153: ...NX50 Troubleshooting Manual Reading Electrical Schematics Page 4 6 Issue 6 0 2019 04 01...
Page 184: ...Issue 6 0 2019 04 01 MD 4 Figure MD 4 NAPI95A 01 Power Module Interface PWB...
Page 188: ...Issue 6 0 2019 04 01 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 192: ...Issue 6 0 2019 04 01 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 198: ...Issue 6 0 2019 04 01 MD 18 Figure MD 18 Fan Tray Assembly 207 8133 B1 B2 J1 AIR FLOW AIR FLOW...
Page 201: ...Issue 6 0 2019 04 01 MD 21 Figure MD 21 NAFP106B 01 Directional Coupler A1 DETAIL...
Page 204: ......