
NG1000 Troubleshooting Manual
Responding to alarms
Page 1-14
Issue 0.4 2010-10-12
TXA (or TXB) Running
Bias
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter is
running its biasing routine, during which time it cannot
produce RF power.
TXA (or TXB) SAME
TXF Inhib
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter is
being inhibited due to receiving a TXF command via
the SAME interface.
TXA (or TXB) SWR
Foldback
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the transmitter system output
probe measures a reflected power greater than
309 W, at rated power (or VSWR of 3.5:1). The active
transmitter has entered a foldback mode to maintain
the reflected power at 309 W or less. The transmitter
will continue to fold back, as necessary, to maintain
this reflected power, until the system VSWR reaches
5.5:1, at which point the system will shut down and
generate a System High VSWR alarm.
TXA (or TXB) SWR
Shutback
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter
measures a high VSWR condition on its output,
causing a complete, but temporary loss of RF output
power.
TXA (or TXB) SWR
Shutdown
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter
shuts down with a complete loss of RF output power
due to repeated cutback, foldback or shutback events.
The system requires a manual reset to recover.
TXA (or TXB) 48V Fail
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the +48 V power supply’s
output voltage is outside the acceptable range of
43.2 V to 52.8 V. Suspect a possible fault with the +48
V power supply (U2).
TXA (or TXB) +15V
Fail
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the +15 V power supply
measured on the exciter/control PWB is outside the
acceptable range of 13.5 V to 16.5 V. Suspect a
possible fault with the +15 V supply circuitry on the
exciter/control PWB (A1).
TXA (or TXB) -15V
Fail
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the -15 V power supply’s
output voltage is outside the acceptable range of
-16.5 V to -13.5 V. Suspect a possible fault with the
-15 V supply circuitry on the exciter/control PWB (A1).
Alarm (with Prefix)
Alarm/Status LED
Description and Troubleshooting Action
Summary of Contents for NG1000
Page 2: ......
Page 4: ......
Page 8: ...NG1000 Troubleshooting Manual Table of contents Page viii Issue 0 4 2010 10 12 ...
Page 10: ...NG1000 Troubleshooting Manual Page x Issue 0 4 2010 10 12 ...
Page 14: ...NG1000 Troubleshooting Manual Page xiv Issue 0 4 2010 10 12 ...
Page 22: ...NG1000 Troubleshooting Manual Page xxii Issue 0 4 2010 10 12 ...
Page 56: ...NG1000 Troubleshooting Manual Responding to alarms Page 1 34 Issue 0 4 2010 10 12 ...
Page 122: ...NG1000 Troubleshooting Manual Wiring connector lists Page 3 10 Issue 0 4 2010 10 12 ...
Page 128: ...NG1000 Troubleshooting Manual Reading Electrical Schematics Page 4 6 Issue 0 4 2010 10 12 ...
Page 153: ...Issue 0 4 2010 10 12 MD 6 Figure MD 6 NAPE82 Exciter Control PWB ...
Page 159: ...Issue 0 4 2010 10 12 MD 12 Figure MD 12 NAPA24 PA PWB C1 C2 C8 Q1 ...
Page 162: ...NG1000 Troubleshooting Manual List of terms Page 6 2 Issue 0 4 2010 10 12 ...
Page 163: ......