![Nautel NG1000 Troubleshooting Manual Download Page 35](http://html1.mh-extra.com/html/nautel/ng1000/ng1000_troubleshooting-manual_711195035.webp)
NG1000 Troubleshooting Manual
Responding to alarms
Issue 0.4 2010-10-12
Page 1-13
TXA (or TXB)
Preamp/IPA Fail
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter’s
IPA has been flagged with a failure condition, due to a
current reading that is less than 50% of nominal or
greater than 150% of nominal. The nominal IPA
current reading is 3.79 A (alarm occurs below 1.90 A
or above 5.68 A). Preamp current is not monitored to
determine a failure condition.
TXA (or TXB) PS A or
B AC Fail
TRANSMITTER A
TRANSMITTER B
This alarm occurs when an associated transmitter’s
power supply module (U3 or U4) detects a PS AC Fail,
caused when the input ac voltage is less than 180 V
ac or above 264 V ac. These fault signals are passed
to the system controller on a serial bus. Check the ac
power source. If it is OK, suspect a fault with the
power supply module (U3 or U4). To replace a power
supply module, see
“Power Supply Module
Replacement” on page 1-17
.
TXA (or TXB) PS A or
B Missing
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated power supply
is not present.
TXA (or TXB) PS A or
B Over Temp
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated power supply’s
internal temperature protection circuit trips, causing it
to be inhibited.
TXA (or TXB) PS Dist
15V Flt
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the +15 V power supply’s
output voltage is outside the acceptable range of
13.5 V to 16.5 V. Suspect a possible fault with the
+15 V supply circuitry on the PS distribution PWB
(A2).
TXA (or TXB) PS Dist
5V Fail
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the +5 V power supply’s
output voltage is outside the acceptable range of 4.7 V
to 5.3 V. Suspect a possible fault with the +5 V supply
circuitry on the PS distribution PWB (A2).
TXA (or TXB) Reject
Foldback
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the output power is being
limited due to excessive reject power.
TXA (or TXB) Resid
PA Volts
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the output power is being
inhibited due to residual voltage on the power supply
(minimum acceptable level is 3 V). This must be
allowed to discharge before turning on again.
TXA (or TXB) RF Off
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter
issues a command to turn itself off.
Alarm (with Prefix)
Alarm/Status LED
Description and Troubleshooting Action
Summary of Contents for NG1000
Page 2: ......
Page 4: ......
Page 8: ...NG1000 Troubleshooting Manual Table of contents Page viii Issue 0 4 2010 10 12 ...
Page 10: ...NG1000 Troubleshooting Manual Page x Issue 0 4 2010 10 12 ...
Page 14: ...NG1000 Troubleshooting Manual Page xiv Issue 0 4 2010 10 12 ...
Page 22: ...NG1000 Troubleshooting Manual Page xxii Issue 0 4 2010 10 12 ...
Page 56: ...NG1000 Troubleshooting Manual Responding to alarms Page 1 34 Issue 0 4 2010 10 12 ...
Page 122: ...NG1000 Troubleshooting Manual Wiring connector lists Page 3 10 Issue 0 4 2010 10 12 ...
Page 128: ...NG1000 Troubleshooting Manual Reading Electrical Schematics Page 4 6 Issue 0 4 2010 10 12 ...
Page 153: ...Issue 0 4 2010 10 12 MD 6 Figure MD 6 NAPE82 Exciter Control PWB ...
Page 159: ...Issue 0 4 2010 10 12 MD 12 Figure MD 12 NAPA24 PA PWB C1 C2 C8 Q1 ...
Page 162: ...NG1000 Troubleshooting Manual List of terms Page 6 2 Issue 0 4 2010 10 12 ...
Page 163: ......