
NG1000 Troubleshooting Manual
Responding to alarms
Page 1-10
Issue 0.4 2010-10-12
Transmitter Generated Faults
TXA (or TXB) AC
Fault
TRANSMITTER A
TRANSMITTER B
This alarm occurs when an associated transmitter’s
power supply module (U3 or U4) detects a PS Ac Fail,
caused when the input ac voltage is less than 180 V
ac or above 264 V ac. These fault signals are passed
to the system controller on dedicated lines. Check the
ac power source. If it is OK, suspect a fault with the
power supply module (U3 or U4). To replace a power
supply module, see
“Power Supply Module
Replacement” on page 1-17
.
TXA (or TXB) All PAs
Failed
TRANSMITTER A
TRANSMITTER B
This alarm occurs when all PAs in the transmitter are
indicating PA Fail alarms.
TXA (or TXB) Audio
Shutdown
TRANSMITTER A
TRANSMITTER B
This alarm occurs during a firmware upgrade. It
indicates that the associated transmitter is not
processing audio because it is undergoing a firmware
upgrade.
TXA (or TXB) Coax
Interlock
TRANSMITTER A
TRANSMITTER BD
This alarm occurs when the coax interlock input from
the system controller is not in the correct state,
inhibiting the associated transmitter’s output.
TXA (or TXB) Comm
Fail
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter is
not responding on the serial bus, indicating lack of
power, a faulty cable or a hardware fault. Check the
serial cables between the system controller and the
associated transmitter.
TXA (or TXB) Cutback
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter has
reduction in RF output power, caused by the
occurrence of multiple shutback events within a pre-
defined time period.
TXA (or TXB) Disch
PA Volts
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter is
taking longer than expected to discharge the voltage
from the power supply after turning off (maximum
acceptable time is 2 s).
TXA (or TXB) Exc
Rebooted
TRANSMITTER A
TRANSMITTER B
This alarm occurs when the associated transmitter’s
exciter reboots. Typically this alarm accompanies a
loss of ac power to the transmitter.
Alarm (with Prefix)
Alarm/Status LED
Description and Troubleshooting Action
Summary of Contents for NG1000
Page 2: ......
Page 4: ......
Page 8: ...NG1000 Troubleshooting Manual Table of contents Page viii Issue 0 4 2010 10 12 ...
Page 10: ...NG1000 Troubleshooting Manual Page x Issue 0 4 2010 10 12 ...
Page 14: ...NG1000 Troubleshooting Manual Page xiv Issue 0 4 2010 10 12 ...
Page 22: ...NG1000 Troubleshooting Manual Page xxii Issue 0 4 2010 10 12 ...
Page 56: ...NG1000 Troubleshooting Manual Responding to alarms Page 1 34 Issue 0 4 2010 10 12 ...
Page 122: ...NG1000 Troubleshooting Manual Wiring connector lists Page 3 10 Issue 0 4 2010 10 12 ...
Page 128: ...NG1000 Troubleshooting Manual Reading Electrical Schematics Page 4 6 Issue 0 4 2010 10 12 ...
Page 153: ...Issue 0 4 2010 10 12 MD 6 Figure MD 6 NAPE82 Exciter Control PWB ...
Page 159: ...Issue 0 4 2010 10 12 MD 12 Figure MD 12 NAPA24 PA PWB C1 C2 C8 Q1 ...
Page 162: ...NG1000 Troubleshooting Manual List of terms Page 6 2 Issue 0 4 2010 10 12 ...
Page 163: ......