3D TRASAR
5500 - Installation & Operation Manual
521-OM0108.88
Copyright
2009 Nalco Company
G-2
Technical Help
(630) 305-CHEM
The High Pressure Water Reinjection System
(P/N
060-TR5540.88
) was designed to enable a 3D TRASAR
controller to be used in high-pressure applications such as High
Rises and Closed Loops. The Reinjection System regulates
the pressure coming into the controller and reinjects the water
back into the same system from which it came. The High Pres-
sure Reinjection System is outfitted with a pressure regulator
that is designed for the inlet water to be a maximum pressure of
300-psi, which will be reduced to an operating pressure of ap-
proximately 75-psi. The pump draws a suction f rom the
3D TRASAR, repressurizing the water and reinjects it back into
the process. The system requires a minimum flowrate of 8gpm.
3. High Pressure Water Reinjection System
High Pressure W ater Reinjection System
shown with 3D TRASAR system.
High Pressure Water Reinjection System Specifications
Plumbing Requirements
•
High Pressure Inlet: 1" FNPT
•
High Pressure Outlet: 1" FNPT
•
Low Pressure Inlet: 1" Hose Barb
•
Low Pressure Outlet: 1" Hose Barb
•
Supply Water: Maximum 300-psi, Minimum 8gpm
Electrical
•
220V, Single Phase, 25A
Alarms
•
Alarm output relay rated for 120V, 1A
Current Protection
•
Preset under-current protection to prevent cavitation
•
Preset over-current protection against over pressurization
Pressure Protection
•
Relief Valve set for 85-psi
Ambient Temperature
•
40-120
o
F (4-50
o
C)
Relative Humidity
•
0-95% non-condensing
Maximum water pressure
•
300psi
Dimensions
• 32"H x 48"W x 12"D
Control Box
• Nema 4x enclosure
Indicator Lights
•
White – Power Light
•
Red – Alarm Light
•
Green – Pump Running Light
Refer to operation manual shipped with high pressure water reinjection system for more details.