![MSA Senscient ELDS 1000 series Operating Manual Download Page 85](http://html.mh-extra.com/html/msa/senscient-elds-1000-series/senscient-elds-1000-series_operating-manual_1846249085.webp)
Installation & Commissioning
Senscient ELDS™
Rev 15
85
GB
RS485
When RS485 is chosen, the screen below instructs you to make the RS485 connections to the
ELDS unit that you want to communicate with. When the necessary RS485 connections have
been made, click
OK
.
Take care to get the RS485 (A) = Purple, and RS485 (B) = Black wires connected to the
correct terminals (A) and (B). The RS485 communications link does not work if you
connect these wires the wrong way around.
If the ‘Power On Unit’ screen below is presented, no RS485 communications were possible with
the ELDS unit. The most likely explanations for no RS485 communications are no power reaching
the ELDS unit or incorrect connection of the RS485 leads. Check the power and RS485
connections and once corrected, re-try RS485 communications by clicking
OK
.