Installation & Commissioning
Senscient ELDS™
Rev 15
59
GB
4.2. Installation Procedure
4.2.1 General
The Senscient ELDS™ 1000 / 2000 Series OPGD is designed to allow installation and alignment
to be performed by a single, trained technician.
The installation procedure is split into mechanical installation and electrical installation. Each unit
needs to be mounted to a supporting structure before making the electrical connections.
4.2.2 Mechanical Installation
The mechanical installation procedure applies to both the Receiver and the Transmitter.
Check that the gas detector equipment supplied is compatible with the required application
(1)
(i.e. correct gas and operating range for application).
Ensure that the Hazardous Area Certification of the equipment supplied is correct for the
(2)
Hazardous Areas / Hazardous (Classified) Locations / Hazardous Zones where the
equipment is to be installed.
Check that the locations selected for siting the equipment are suitable - see section 3.2
(3)
For each unit (Tx and Rx) fix the mounting bracket using one of the procedures described in
(4)
the following sections.
Wall Mounting
Summary of Contents for Senscient ELDS 1000 series
Page 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Page 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Page 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Page 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Page 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Page 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...