Appendix C – Functional Testing Using Gas
Senscient ELDS™
Rev 15
157
GB
Fully insert the cell as illustrated below:
Verify the response of the Cross Duct ELDS system being tested by monitoring the system’s
4-20mA output or the gas reading using SITE. After completing the test, remove the Gas
Challenge Cell and replace the Challenge Cell Aperture Cover.
GAS TEST CELL
CORRECTLY LOCATED