Appendix F – MODBUS Communications
170
Senscient ELDS™
Rev 15
GB
There are 5 single bit Coils (or bit input/output registers) as follows.
Coil
Applies Content
1
Tx
Implement Undisclosed Simu-Gas(with marker), Coil will return to zero
once Tx has completely finished the process. Note, following setting
the value subsequent reads will show the Coil value still at zero for
about 10 seconds. The value will be asserted once the SimuGas
process (timer driven in the Firmware) starts. The value then remains
asserted for about 1½ minutes whilst the Simu-Gas is operating
2
Tx
Implement disclosed Simu-Gas (no marker), Coil will return to zero
once Tx has completely finished the process
3
Rx
Assert Test values to 4-20mA outputs, must write zero back to this coil
to revert to gas monitoring.
NOTE
: The controller must ensure that this value is written back to
zero as otherwise the ELDS Receiver will not be able to monitor gas.
The actual test current is specified by Holding register 7 (see below).
4
Rx
L0 Zero Calibration, value will be reset to 0 once zero completed
5
Rx
L1 Zero Calibration, value will be reset to 0 once zero completed
These are read/write bit data and can be read using the Modbus command 0x01 (Read Coils) and
can be written using commands 0x05 (Write Single Coil) or 0x0F (Write Multiple Coils).
Each of these registers are available on both ELDS Transmitter and Receiver units, however 1
and 2 only ‘apply’ to Transmitter units; whilst 3, 4 and 5 only ‘apply’ to Receiver units.
There are 41 Input Registers. These are all 16 bit (unsigned) quantities as follows:
Input
Applies
Content
Comment
1
Rx
L0 Gas Value, ppm
ppm.m
2
Rx
L1 Gas Value, ppm
3
Tx & Rx
L0 Full Scale Range
ppm.m
4
Tx & Rx
L1 Full Scale Range
5
Tx & Rx
Firmware Major Version
6
Tx & Rx
Firmware Minor Version
7
Tx & Rx
Firmware Build Version
8
Tx & Rx
Unit Serial Number
Serial Numbers are Factory Set
9
Tx & Rx
Paired Unit Serial Number
10
Rx
L0, Last Simu-Gas Result
ppm.m
11
Rx
L1, Last Simu-Gas Result
12
Rx
L0 Signal ValueA
Signal = ValueA×ValueB/1000, units are
internal ELDS scale
13
Rx
L0 Signal ValueB
14
Rx
L1 Signal ValueA
15
Rx
L1 Signal ValueB
16
Rx
L0 Gas ValueA
Gas = ValueA×ValueB/1000, units are
ppm.m
17
Rx
L0 Gas ValueB
18
Rx
L1 Gas ValueA
19
Rx
L1 Gas ValueB
20
Rx
Last SG Year
base 2000, so 2011 would be represented
by the year value 11
Summary of Contents for Senscient ELDS 1000 series
Page 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Page 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Page 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Page 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Page 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Page 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...