Installation & Commissioning
Senscient ELDS™
Rev 15
81
GB
Insert the XD Alignment Sight into the slot of either the TX or RX unit to be aligned.
(5)
Switch on the red dot of the alignment sight by rotating the corresponding knob on the sight.
(6)
Insert the fluorescent target holder into the slot of the TX or RX unit opposite, to which you
(7)
are about to align the XD unit.
Gradually tighten either one of the two M6 mounting / adjustment bolts intended to provide
(8)
vertical alignment adjustments; whilst observing the position of the red dot with respect to the
fluorescent target.
Make vertical and horizontal adjustments until the red dot is in the centre of the circular
(9)
fluorescent disc.
XD Alignment
Sight
Fluorescent
Target Disc