Installation & Commissioning
Senscient ELDS™
Rev 15
101
GB
There is now a short delay while SITE completes the writing of necessary information to the Rx
unit. Once this is done the following confirmation is presented; acknowledge this by clicking
OK
.
The installation is now complete.
10) Final steps (RS485)
Disconnect the RS485 A and B leads from the Transmitter’s terminal block.
Carefully replace the terminal compartment lid and screw it down firmly.
Once the terminal compartment lid is properly screwed down, attach and lock-off the anti-
tamper fixture.
CAUTION
Both the explosion-proof protection and the ingress protection of the ELDS OPGD system rely
upon the terminal compartment lid being screwed down fully. The lid should be tight and the O-
ring compressed when the lid is properly screwed down.