![MSA Senscient ELDS 1000 series Operating Manual Download Page 132](http://html.mh-extra.com/html/msa/senscient-elds-1000-series/senscient-elds-1000-series_operating-manual_1846249132.webp)
Specifications
132
Senscient ELDS™
Rev 15
GB
8. Specifications
8.1. System
Gases & Ranges
For Methane, the following LFL concentrations are assumed. Units are appropriately calibrated in
the factory depending on the required certification.
Certification
%v/v for 1LFL
ATEX, IECEx, GOST-R, GOST-K, InMetro
4.4
CSA(UL)
5.0
Gases, Ranges & Path Lengths
ELDS Receiver units contain two 4-20mA current loops that are used to signal gas levels.
For dual gas units each loop is used for an individual gas, however for single gas units the
second output loop will provide an alternative measurement of the gas measurement; and
this may be of a different full scale to the primary output. Details of this are contained in the
following table. A full specification of the different ranges for each output is provided for
each ELDS part number in Appendix H.
Gas
Open Path Ranges
Available Path Lengths
Methane (CH
4
)
0-1 / 0-1 LFL.m,
0-5 / 0-1 LFL.m
0-1,000ppm.m / 0-1 LFL.m
5-40m, 40-120m, 120-200m
Methane (CH
4
) &
Hydrogen Sulphide (H
2
S)
0-1 LFL.m (CH
4
)
0-250 ppm.m (H
2
S)
0-500 ppm.m (H
2
S)
0-1,000 ppm.m (H
2
S)
0-15,000 ppm.m (H
2
S)
5-60m
Hydrogen Sulphide (H
2
S) 0-250 / 0-500 ppm.m
0-500 / 0-1000 ppm.m
0-1,000 / 0-5000 ppm.m
0-1,500 / 0-5000 ppm.m
0-5,000 / 0-10,000 ppm.m
0-15,000 / 0-500 ppm.m
5-60m
Hydrogen Fluoride (HF)
0-25 / 0-100 ppm.m
(Only 5-60m Path Length)
0-50 / 0-100 ppm.m
0-200 / 0-100 ppm.m
0-1,000 / 0-500 ppm.m
5-60m, 60-120m
Ammonia (NH3)
0-1,000 / 0-500 ppm.m
0-5000 / 0-1000 ppm.m
5-40m, 40-120m
Hydrogen Chloride (HCl)
0-50 / 0-100 ppm.m
5-60m
Carbon Dioxide (CO
2
)
0-300,000 / 0-100,000 ppm.m
5-40m, 40-120m
Ethylene (C
2
H
4
)
0-1 / 0-1 LFL.m,
0-10,000ppm.m / 0-1LFL.m
5-40m, 40-120m, 120-200m
Summary of Contents for Senscient ELDS 1000 series
Page 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Page 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Page 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Page 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Page 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Page 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...