Power Supply Connections, Wiring & Fuses
The Senscient ELDS™ gas detector is designed to be operated from a nominal 24V DC supply.
For correct operation, the supply voltage reaching the terminals must be within the range
18V to 32V.
The unit maximum power consumption and cable lengths are as follows:
Component
Maximum Power
Consumption, W
Maximum Cable Length,
m with 1.5mm
2
Conductors (12Ω/km)
Maximum Cable Length,
m with 2.5mm
2
Conductors (7.6Ω/km)
Receiver
10W
450
710
Transmitter
12W
375
590
Control room supply voltage assumed to be +24V.
Terminal sizes:
Transmitter
0.5mm
2
- 2.5mm
2
(20AWG - 14AWG)
Receiver
0.5mm
2
– 2.5mm
2
(20AWG - 14AWG)
In order to avoid power supply interruptions due to fuse ageing / degradation, it is advisable to use
a fuse in the power feed to the ELDS units that is sufficiently de-rated. The recommended fuse
ratings for the power supply feeds to ELDS units are therefore as follows:
ELDS Unit(s) Supplied
Minimum Fuse Rating
Recommended Fuse Rating
Receiver (1)
0.75A
1A
Transmitter (1)
1A
1.5A
Receiver (1) plus Transmitter (1)
1.75A
2.0A
Summary of Contents for Senscient ELDS 1000 series
Page 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Page 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Page 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Page 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Page 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Page 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...