Problem Solving
124
Senscient ELDS™
Rev 15
GB
Info.
The Info. Box contains information about the SimuGas Auto Event Time, Status and Time & Date
of the Transmitter with which SITE is communicating.
The
SimuGas Auto Event Time
is the time when the next SimuGas Auto test is scheduled to be
performed automatically by the Transmitter.
The
Status
descriptor provides information upon the operational status of the Transmitter.
Ordinarily, the Transmitter status should be ‘system running’, which means that the laser diode(s)
of the Transmitter are correctly locked up on their respective target gas(es) - ready for the
detection of gas should any enter the beam-path. During execution of the start-up and laser
locking procedures, the status descriptor provides information as to where the Transmitter is within
these procedures.
STATUS
DESCRIPTION
System Running
The transmitter is up and running correctly with its laser(s)
locked onto target gas
Hunting For Gas
The transmitter is performing the gas lock hunting procedure.
Gas Hunt Complete
The transmitter has successfully completed the gas lock hunting
procedure.
Full Gas Search
The transmitter is executing a full gas search in order to lock its
laser(s) on target gas(es).
Failed Gas Search
The transmitter has performed a full gas search and failed to
identify and lock onto the target gas(es).
Diffuser Failed
The transmitter diffuser has failed.
Not Installed
The system has not been successfully installed and is not
operational.
SimuGas Active
A SimuGas Live or SimuGas Auto test is being performed.
Ambient TEC at Temperature
The ambient TEC has reached the correct temperature.
Laser Diode TEC at
Temperature
The laser diode TEC has reached the correct temperature.
The
Time & Date
are the time and date being reported by the Real Time Clock of the Transmitter
with which SITE is communicating.
Summary of Contents for Senscient ELDS 1000 series
Page 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Page 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Page 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Page 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Page 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Page 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...