![MSA Senscient ELDS 1000 series Operating Manual Download Page 12](http://html.mh-extra.com/html/msa/senscient-elds-1000-series/senscient-elds-1000-series_operating-manual_1846249012.webp)
System Description
12
Senscient ELDS™
Rev 15
GB
When designing an installation for Senscient ELDS™ 1000 / 2000 Series it is important
that the correct range of the gas detector for each path to be monitored is selected and
specified.
In order to avoid the problems associated with gas detectors being used beyond their
specified ranges or when incorrectly aligned, a procedure within the Senscient
Installation & Test Environment (SITE) checks for correct gas detector type, operating
range and signal levels before allowing an ELDS OPGD to be commissioned.
The Transmitter and Receiver are each mounted upon robust, adjustable mounting brackets. The
design of the mounting and alignment arrangement for the Senscient ELDS™ 1000 / 2000 Series
is highly accommodating, making it simpler to realise a good installation in a variety of locations
and environments. Installation details are given in section 3.
2.2. Transmitter
The Senscient ELDS™ Transmitter produces up to two controlled-divergence beams of infrared
laser light from solid-state laser diodes. The outputs from the laser diodes are partially collimated
using a faceted lens, the facets of which introduce the controlled-divergence that is necessary to
reduce system alignment sensitivity. The Transmitter operates continuously.
THE TRANSMITTED LASER BEAM IS CLASS 1 (EYE-SAFE) PER IEC 60825.
The Transmitter contains a small retained sample of the target gas(es) to be detected by the
system; and uses this retained sample as a reference to maintain its laser diode(s) in Harmonic
Fingerprint lock. By continuously maintaining Harmonic Fingerprint lock it is possible to be certain
that whenever target gas(es) enter the system’s beam-path this will introduce Harmonic
Fingerprints onto the laser signal(s), which will be seen and measured by the Receiver.
Maintaining Harmonic Fingerprint lock maintains detector calibration and ensures that SimuGas™
simulations faithfully simulate the presence of a pre-defined quantity of target gas(es) in the beam-
path. This is the basis of the SimuGas on-demand functional test technology incorporated in
Senscient’s ELDS OPGDs.
220mm
300mm
245mm
Summary of Contents for Senscient ELDS 1000 series
Page 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Page 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Page 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Page 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Page 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Page 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...