13 Technical data
Maschinenfabrik Reinhausen GmbH 2022
182
8595028/00 EN
TAPCON
®
250
Overload capacity short-term
120 A/1 s (directly on the test tap of the measure-
ment card)
Surge test voltage
4 kV, measurement category III
13.1.6 Ambient conditions
Operating temperature
-25...+70°C
Storage temperature
-30...+85°C
Relative humidity
5...95%, condensation not permitted
Maximum installation alti-
tude
<3,000 m above mean sea level
Minimum clearance to
other devices / control
cabinet
Cap rail modules:
Above/below: 30 mm (3.5 in; equivalent to 2RU), behind
30 mm (1.2 in)
Left/right: 30 mm
WEB panel:
Rear 30 mm (1.2 in)
Contamination level
2
Protection class
1 (protective conductor connection)
Table 58: Permissible ambient conditions
13.1.7 Standards and directives
Electromagnetic compatibility
IEC 61000-6-2; IEC 61000-6-4;
IEC 61000-6-5;
KS C 9610-6-2; KS C 9610-6-4
FCC 47 CFR Part 15 B
Radiocommunication Act – IECS-003
Electrical safety
IEC 61010-1; UL 61010-1; CSA-C22.2
No. 61010-1
IEEE CB scheme procedure
Climatic ambient conditions
IEC 60068-2-1 (-25°C; 96 h) cold
IEC 60068-2-2 (+70°C; 96 h) dry heat
IEC 60068-2-78 (+40°C / 93% rH, 96 h)
moist heat, constant
IEC 60068-2-30 (+55°C, 6 cycles 12 +
12 hours) moist heat, cyclical
Degree of protection
IP20
Environmental durability tests