9 Operation
Maschinenfabrik Reinhausen GmbH 2022
105
8595028/00 EN
TAPCON
®
250
Description
O: AVR Local/Remote
If a signal is present at the input, the de-
vice activates the LOCAL/REMOTE
function.
O: Status Ok
If a signal is present at the input, the de-
vice activates the device status.
O: Lower
If a signal is present at the input, the de-
vice activates the LOWER function.
O: Raise
If a signal is present at the input, the de-
vice activates the RAISE function.
O: TDSC® active
If a signal is present at the input, the de-
vice activates the TDSC® function.
9.1.8.4 Linking digital outputs
You can link each event with a digital output. The device provides 5 digital
outputs (GPO) for this purpose. When you link a digital output to an event,
the device issues a signal to this output if the event occurs. The signal per-
sists until the event stops. A parameter is available for each available digital
output.
To forward input signals or control system commands, you need to link the
digital outputs or control system messages with the
General purpose input
or
Generic SCADA command
events.
ü
The desired event number is known.
1. Go to
Settings > Parameters > System > Link outputs
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
Generic digital output X
You can use this parameter to link the digital output with an event message.
To do so, enter the desired event number.
If you enter event number 500, the link is disabled.