9 Operation
Maschinenfabrik Reinhausen GmbH 2022
99
8595028/00 EN
TAPCON
®
250
The digital inputs available are each permanently linked to a
General pur-
pose input
event message and the control system commands available are
each permanently linked to a
Generic SCADA command
event message for
this purpose.
Input/command
Event message
Digital input 1
General purpose input 1
Digital input 2
General purpose input 2
...
...
Generic SCADA command 1
Generic SCADA command 1
Generic SCADA command 2
Generic SCADA command 2
...
...
Table 21: Linking of digital inputs and control system commands with event messages
You can link the event messages with device functions, digital outputs and
control system messages. You can also link all other event messages (e.g.
Undervoltage U<
) with digital outputs and control system messages. Corre-
sponding parameters, for which you need to enter the relevant event num-
ber, are provided for this purpose.
9.1.8.1 Linking functions
You can link the
General purpose input
or
Generic SCADA command
events
with device functions. This allows you to remotely control the device using
digital inputs or commands via the control system (SCADA).
To establish the link, you have to enter the corresponding event number in
the desired parameter.
Note that you can only enter the event numbers of the
General purpose in-
put
or
Generic SCADA command
events.
If you enter event number 500, the link is disabled.
ü
The desired event number is known.
1. Go to
Settings > Parameters > System > Link functions
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
Local/Remote
The assigned event activates LOCAL or REMOTE mode on the device.
Blocking
If the assigned event is active, automatic control is blocked.