9 Operation
Maschinenfabrik Reinhausen GmbH 2022
108
8595028/00 EN
TAPCON
®
250
Property
Options
Decimal places
1)
Set up to three decimal places.
Minimum/maximum
value
Set the minimum and maximum values of the sensor, e.g.
with a 4...20 mA signal, the corresponding measured
value for 4 mA and the corresponding value for 20 mA.
Correction factor
2)
Set the correction factor (m) for the correction of the func-
tion value (x). The corrected function value (y) is:
y = (m * x) + t
Correction offset
2)
Set the offset (t) for the correction of the function value
(x). The corrected function value (y) is: y = (m * x) + t
Table 22: Configuration of the analog inputs and outputs
1)
Only available for AIO.
2)
Only available for inputs.
You can only change the configuration of the analog inputs if you have a
Parameter Configurator or Administrator role.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
Creating a backup
You need to create a backup to be able to reset the system in the event that
any incorrect configuration settings are made.
1. Go to
Settings > Export
.
2. Go to the option
Settings
to export a backup copy of the current settings.
3. Select the desired
interface
.
4. Press the
Export
button to start the export.
Configuring AIO
1. Go to
Settings > AIO configuration
.
2. Configure properties such as
function
,
signal type
and
card/channel
.
3. Select the
button to configure the values as desired.
4. Press the
Accept
button.
5. Confirm the security prompt with
Save
to save the changes.