9 Operation
Maschinenfabrik Reinhausen GmbH 2022
86
8595028/00 EN
TAPCON
®
250
If you deactivate the service user access and lose your password for the ad-
ministrator role, it is not possible to reset the administrator password. If the
administrator password is lost, the device must be reset to the default set-
tings. When doing so, all information stored on the device (parameters,
measured values, etc.) will be lost.
You must be assigned the administrator role to set parameters.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
1. Go to
Settings > Parameters > System > General > Service user ac-
cess activation
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
4. Restart the device to adopt the change.
Service user access activation
You can use this parameter to activate or deactivate service user access.
9.1.2 Configuring the network
You can use this menu item to configure the necessary network interface.
You must wire the device in accordance with the respective control system
protocol. The following protocols are available:
1. Go to
Settings > Parameters > System > Network settings
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
IP address
You can use this parameter to assign an IP address to the device.
Assign IP addresses to both web-based visualization and SCADA (optional)
in different subnets. Otherwise you will not be able to establish a connec-
tion.
Subnet mask
You can use this parameter to set the subnet mask.